Riello Burners CAMRAY5 150 Installation, Use And Maintenance Instructions Download Page 1

2902785 (4)

Installation, use and maintenance instructions

Kerosene and light oil burners

One stage operation

 

  

CODE

BOULTER CODE

MODEL

TYPE

3748960

8-716-108-334

CAMRAY5 150/200

490 T51

3748961

8-716-108-333

CAMRAY5 200/240

490 T51

3748962

8-716-111-556

COH 280

490 T51

Summary of Contents for CAMRAY5 150

Page 1: ...aintenance instructions Kerosene and light oil burners One stage operation CODE BOULTER CODE MODEL TYPE 3748960 8 716 108 334 CAMRAY5 150 200 490 T51 3748961 8 716 108 333 CAMRAY5 200 240 490 T51 3748962 8 716 111 556 COH 280 490 T51 ...

Page 2: ...ng 7 4 6 Combustion head setting 8 4 7 Air damper adjustment 8 4 8 Burner start up cycle 8 5 FAULTS SOLUTIONS 9 6 SAFETY WARNINGS 10 6 1 Burner identification 10 6 2 Basic safety rules 10 In case of BF applications the intake air temperature must not be over 70 C CE Certification No 0036 0332 02 as 92 42 EEC Burner with CE marking in conformity with EEC directives EMC 89 336 EEC Low Voltage 73 23 ...

Page 3: ... 20 C Hi 11 86 kWh kg Electrical supply Single phase 50Hz 230V 10 Motor Run current 1 3A 2750 rpm 288 rad s Capacitor 5 µF Ignition transformer Secondary 8 kV 16 mA Pump Kerosene maximum pressure 10 bar 145 psi Light oil maximum pressure 15 bar 218 psi Absorbed electrical power 0 16 kW Burner Flange 167 69 5 253 32 11 204 D4267 83 83 268 163 4 5 4 5 189 168 140 106 Ø 95 0 4 Pressure in the combust...

Page 4: ...iden if necessary the insulating gasket holes 5 see fig 3 Fix the flange 1 to the boiler door 4 using screws 2 and if necessary the nuts 3 interposing the insulating gasket 5 see fig 4 3 2 MOUNTING THE BURNER 5 1 2 4 3 E9188 Fig 2 D5012 Fig 3 E9187 1 Fig 4 In case of BF applications the combustion air supply is trough a flexible tube connected at the socket A E1557 A Fig 5 ...

Page 5: ... 15 8 6 100 100 100 90 70 30 20 1 Suction line 2 Return line 3 By pass screw 4 Gauge connection 5 Pressure adjuster 6 Suction gauge connection 7 Valve 8 Auxiliary pressure test point PRIMING PUMP On the system in fig 7 it is sufficient to loosen the suction gauge connection 6 fig 6 and wait until oil flows out On the systems in fig 8 and 9 start the burner and wait for the priming Should lock out ...

Page 6: ...Black White Blue PE Ignition electrodes 4 pin plug 4 pole socket Burner earth TESTING Check the shut down of the burner by open ing the thermostats and the lock out by dark ening the photoresistance Limit Safety Remote lock out signal 230V 0 5A max thermostat thermostat ATTENTION Do not swap neutral and phase over follow the dia gram shown carefully and carry out a good earth con nection The secti...

Page 7: ...lavan type W B not for 45 light oil Steinen type S Danfoss type S Use Delavan type W CSA 4 3 PUMP PRESSURE The pump leaves the factory set for kerosene working 10 bar maximum pressure for kerosene FOR LIGHT OIL INCREASE PRESSURE 12 bar pressure suitable for light oil in most cases 14 bar improves flame retention it is therefore suitable for ignitions at low temperatures FUEL Nozzle Pump pressure B...

Page 8: ...lder 6 after loosing its fixing screw 7 Once replacement of the nozzle has been made screw it and tighten it as shown in the figure 11 4 5 DIFFUSER DISC AND ELECTRODES SETTING see fig 12 E9189 E9191 1 2 3 2 5 4 Fig 11 7 6 To ad just the diffu ser dis c u nit p roceed as follows Loosen the screw 1 fig 12 Move the diffuser disc unit up to level Tighten the screw 1 To adjust the electrodes unit proce...

Page 9: ...ffuser tends to reduce This setting is not advis able for ignitions at low temperatures Tighten the two screws In the sketch on the right the combustion head is adjusted at set point 3 5 Combustion head settings indicated in the schedule at page 6 are valid for most cases 4 7 AIR DAMPER ADJUSTMENT The settings indicated in the schedule refer to the combustion chamber with zero depression These reg...

Page 10: ...uction enclosed with the burner or due to the intervention of unqualified personnel FAULTS POSSIBLE CAUSES SOLUTION The burner will not start when the limit thermostat closes Lack of electrical supply Check presence of voltage in the L N clamps of the control box Check the conditions of the fuses Check that safety thermostat is not lock out The photoresistance sees false light Eliminate the light ...

Page 11: ...late is tampered with removed or missing the product cannot be clearly identi fied thus making any installation or maintenance work potentially dangerous 6 2 BASIC SAFETY RULES Children or inexpert persons must not use the appliance Under no circumstances must the intake grids dissipation grids and ventilation vents in the installation room be covered up with cloths paper or any other material Una...

Page 12: ...bios MOD COD BOULTER COD TIPO TYPE TYP CAMRAY5 150 200 3748960 8 716 108 334 490 T51 CAMRAY5 200 240 3748961 8 716 108 333 490 T51 COH 280 3748962 8 716 111 556 490 T51 Bruciatori di kerosene gasolio Kerosene light oil burners Brûleurs kérosène fioul Kerosin Öl Gebläsebrenner Quemadores de kerosene gasóleo ...

Page 13: ...COIL SHELL AND KNOB BOBINE V M ETRIER ET ECROU M V SPULE HALTEBÜG MIT SCHRAUBE BOBINA PROTECCIÓN BOBINA A 22 3008851 COLLEGAMENTO LEAD COIL CABLE DE CONNEXION ANSCHLUßKABEL MAGNETSPULE CABLES ELECTROVÁLVULA 23 3008654 POMPA PUMP POMPE ÖLPUMPE BOMBA C 24 3000439 ORGANO DI TENUTA PUMP SEAL ORGANE D ETANCHEITE DICHTUNGSEINSATZ ANTRIEBSWELLE CONJUNTO ESTANQUIDAD A 25 3008653 FILTRO ANELLO OR FILTER O ...