5.5.2.2
Wiring diagram
For the power supply of the converter
SAFERUN
® CMS-T must al-
ways be used a certified repeater power supply (3-wire circuit) in
the "intrinsically safe IA or IB".
The following table lists an approved device:
Type
EC-Type Examination
Certificate
Manufacturer
IM33-11Ex-Hi
TÜV 00 ATEX 1595
Hans Turck
IM33-12Ex-Hi
TÜV 00 ATEX 1595
Hans Turck
With the use of an explosion-proof supply isolator the safe elec-
trical isolation of the intrinsically safe supply or supply and signal
circuit of the non-intrinsically safe circuits (eg Power and output
circuit) in accordance with DIN VDE 0106 part 101 and protection
class II guaranteed.
NOTE
►
If the converter
SAFERUN
® CMS-T was sup-
plied only briefly once with a non-intrinsically
safe power supply, the safety-related mark-
ings regarding the explosion protection on
the nameplate have to become unreadable.
►
The subsequent operation of the converter
SAFERUN
® CMS-T in the hazardous area is no
longer permitted for reasons of safety with
regard to the ex-relevant components to help
ensure explosion protection in the Ex i-cir-
cuits.