To ensure safe operation of the
SAFERUN®
CMS-T, the following
notes must be observed:
NOTE
SAFERUN connection cable should:
►
grounded free of potential across the screen
(Avoidance of stray currents)
►
be shielded (Reduction of capacitive cou-
plings)
►
be connected directly to the feed separator
via a continuous cable (no extension with sec-
ond cable or similar) (Avoidance of stray cur-
rents)
►
do not connect to earth / ground via the neg-
ative pole (Avoidance of stray currents)
NOTE
Frequency converter should:
►
grounded potential-free (Avoidance of stray
currents)
►
be equipped with inductor and filter (Avoid-
ance of sources of interference)
►
be connected to the motors via shielded ca-
bles (Reduction of capacitive couplings)
NOTE
Data cables (like that to the SAFERUN) and
power lines should:
►
be separated or at a certain distance (avoid-
ance or reduction of galvanic, capacitive and
inductive coupling, observe the relevant
standards (installation paths, order separa-
tion, shielding of the cable support, ...))