ID No. 9230-020-en
Version 02 (2020-04)
Page 59
6.5.6
Events output signal
The output signal of the
SAFERUN
®
CMS-T converter can be used
to assign specific pump states to fixed, impressed currents.
These fixed current values can be used for example for error
detection in process control technology.
The following parameters are intended for special events:
ID.-#
Parameter name
Event
Standard
value mA
2)
260
iErrorStop
Pump shutdown
3.0
261
iErrorTemp
1)
Temperature sensor error
21.0
262
iErrorSensor
Magnetic sensor
2.5
263
iErrorCouplingbreak
Coupling break / overload
21.5
265
iErrorCouplingMax
Nominal torque exceeded
21
267
IErrorSpeedMin
Speed too low for a reliable evaluation
3.5
268
IErrorSpeedMax
Speed too high for a reliable evaluation
20.5
269
IErrorClock
Date / time error
-1.0
1)
If the temperature is output via the 4-20 mA signal (output
mode = 10, ID.# 210), the event
“
Temperature sensor error
”
(IError Temp, ID.# 201) cannot be deactivated by -1.0.
With an event of 1.0, 21.0 mA is output in the case of an
event.
2)
The permissible range of values is between 0-4 mA and
20-21.5 mA. The value -1.0 deactivates the event.
In normal operation (ID.# 210, output mode =0), a temperature
sensor error is not output as an event (unless at least one of the
parameters 180 to 184 is in use).
Summary of Contents for SAFERUN CMS-S
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 100: ......
Page 101: ......
Page 102: ......
Page 103: ......
Page 104: ......
Page 105: ......