background image

Series MNK-B, 

size 25-25-100 

Page 13

 

 
 

9230-056-en 

Revision   14 

TM 9542

 

Edition   06/2016 

Commissioning/Shutdown 

6.1  Initial commissioning 

Normally,  the  pumps  have  already  been  test-run  with 
water.  Unless  special  agreements  have  been  made, 
there  could  still  be  residual  amounts  of  water  in  the 
pump.  This  must  be  noted  in  view  of  a  possible 
reaction with the medium. 

 
 

6.1.1  Filling the pump housing 

  Check  to  see  whether  the  screws  on  the  suction 

flange,  discharge  flange,  housing  flange  and  drain 
flange are tightened.  
For screw tightening torques see 

Section 1.1

  Open the suction line fully so that the medium can 

flow into the pump. 

  Open  the  discharge  valve  so  that  the  air  in  the 

pump can escape. 

  If air cannot be vented into the discharge line, e.g. 

a  drop  in  pressure  in  this  line  is  not  permitted, 
venting  must  be  performed  upstream  of  the 
discharge valve. 

  Monitor  the  venting  operation  until  no  air  but  only 

liquid emerges. 

  Close  the  discharge  valve  again  until 

only  the  minimum  flow  rate  is  obtained 
after the motor has been started. 

 
 

6.1.2  Start-up 

  Check  the  direction  of  rotation  of  the 

motor with a rotary field instrument. 

  As  viewed  from  the  motor,  the  direction 

of  rotation  of  the  pump  is  clockwise.  See  also  the 

direction of rotation arrow

 of the pump. 

If  no  rotating  field  instrument  is  available,  the 
motor  may  also  be  activated  briefly,  with  the 
pump  filled,  so  that  it  does  run  up.  You  can 

observe the direction of rotation through the fan hood. 

The  pump  must  not  run  dry  during  the  check 
of the direction of rotation. 
The pump must be completely filled with liquid. 

The  maximum  admissible  flow  rate  must  not  be 
exceeded. 

 

Otherwise  the  plain  bearings  can  run  dry  in 
both cases. 

 

  Switch the motor on. 

  Set  the  desired  flow  by  opening  the  discharge 

valve. 

When the motor is running but the pump is not 
conveying, this means that the magnetic drive 
has stopped. 

  Switch  motor  off  immediately  in  order  to  prevent 

overheating  of  the  magnet  drive  and  the  back 
plate. 

Then proceeded as follows: 

  Close  discharge  valve  down  to  the  position 

"minimum flow rate". 

  Start motor again. 

If the magnetic drive stops again, look for the cause. 

 
 

6.2  Operating limits 

The operating limits of the  pump/unit  in  terms 
of  pressure,  temperature,  power  and  speed 
are  entered  in  the  data  sheet  and  it  is 

imperative to observe them! 

 
 

6.2.1  Abrasive media 

If  liquids  with  abrasive  constituents  are 
conveyed,  increased  wear  at  the  pump  is  to 
be  expected.  The  inspection  intervals  should 

be reduced compared with the usual times. 

 
 

6.2.2  Min./max. flow rate 

The  operating  range  generally  recommended  lies  at 
0.3 Q

opt

  to  1.1 Q

opt

.  Consult  the  manufacturer  for 

operation  outside  this  range.  and  observe 

Section 

2.6.2.

 

 
 

6.3  Shutdown 

  Close  discharge  valve  down  to  the  position 

"minimum flow rate". 

  Switch motor off. 

  Close discharge valve completely. 

Only  close  the  suction  line  if  the  pump  is  to  be 
evacuated or dismantled. 

 

For  all  work  on  the  machine,  make  sure  that 
the  motor  cannot  be  inadvertently  switched 
on. 

 

If  the  pump  is  to  be  evacuated  or  flushed, 
observe the local regulations. 

 

If  the  pump  has  been  operated  with  a 
chargeable  liquid,  it  must  be  filled  with  inert 

gas  (e.g.  nitrogen)  to  prevent  an  explosive 
atmosphere. 

It  is  recommended  to  wait  one  hour  before  the  pump 
is  dismantled  from  the  plant  to  permit  static  peak 
charges to be eliminated. 

These measures are not necessary with pumps with a 
conductive plastic lining. 

If  the  pump  is  returned  to  the  manufacturer's,  clean 
the pump very thoroughly. 
See also 

Section 3.1

Summary of Contents for MNK-B Series

Page 1: ...ctly observed before transport installation operation and maintenance Subject to change without notice Reproduction is generally permitted with indication of the source Richter Chemie Technik GmbH 923...

Page 2: ...5 4 Piping 10 5 4 1 Nominal size 10 5 4 2 Nozzle loads 10 5 4 3 Suction line 11 5 4 4 Supply lines 11 5 4 5 Discharge line 11 5 4 6 Venting and evacuating 11 5 5 Pipe fittings 11 5 6 Monitoring facili...

Page 3: ...of CFRP PTFE Flange connecting dimensions DIN EN 1092 2 type B ISO 7005 2 type B PN 16 or flanges drilled to ASME 16 5 Class 150 ATEX Directive 2014 34 EU Machine Directive 2006 42 EC Materials Press...

Page 4: ...nning ATEX and housing markings The stainless steel type plate is firmly riveted to the housing If the operator attaches his identification it must be ensured that the pump matches the application in...

Page 5: ...n potentially explosive areas special attention is to be paid to the sections identified with Ex in this operating manual 2 1 Intended use Richter pumps of the series MNK B are plastic lined magnetic...

Page 6: ...or enabled immediately after the end of work In the assemble state if the safety notes see also Section 5 1 and 7 5 2 are observed the magnetic drives do not cause any risks or have any affect on the...

Page 7: ...ample of the identification of the pump section II2GD IIC TX X For assembling the pump with components which are not explosion protected e g motor shaft coupling it is recommended to mask or remove th...

Page 8: ...re missing max 40 C is to be assumed Table 2 below indicates the admissible medium temperature depending on the pump design as a function of the temperature class in accordance with EN 13463 1 Table 2...

Page 9: ...onment due to the medium or oil Wear protective clothing when work is performed on the pump Prior to the disposal of the pump Collect any medium oil etc which has escaped and dispose of it in accordan...

Page 10: ...te 5 4 Piping Before the pump is installed both the suction and supply lines as well as the discharge line are to be cleaned Dirt or damage to the sealing surfaces is best avoided if the flange covers...

Page 11: ...of the medium can if necessary be reduced 5 4 6 Venting and evacuating Venting can take place into the discharge line or upstream of the discharge valve A venting line can also be used as a bypass dr...

Page 12: ...the installation drawing The operating manual of the motor manufacturer must be observed A motor with a valid ATEX certificate is to be used if employed in zone 1 and 2 5 8 Electric connection The ope...

Page 13: ...he plain bearings can run dry in both cases Switch the motor on Set the desired flow by opening the discharge valve When the motor is running but the pump is not conveying this means that the magnetic...

Page 14: ...uction line not opened or not opened fully Pump is cavitating material damage to pump and plain bearings Pump does not attain the required delivery head or flow rate Pump may be destroyed due to overh...

Page 15: ...available Has the pump been taken out of operation evacuated and flushed correctly See also Section 6 3 If no new assembly is performed immediately after dismantling the plastic and ceramic component...

Page 16: ...ern Remove hex screw 901 9 with disc 550 1 Pull flywheel mass 599 off the motor shaft Unscrew lantern 344 with hex socket screw 914 3 and washer 554 8 off the motor 7 7 Notes on assembly Use original...

Page 17: ...ssembly with the back plate 161 Insert the back plate with the impeller 230 into the lantern 344 Insert intermediate ring 509 1 into the lantern 344 Insert housing gasket 401 Screw housing 100 to slid...

Page 18: ...led and cleaned Have any strainers installed been cleaned Are all shut off devices open Is the geodetic head too high Is the NPSHA too low or the NPSHR too high Are the pipe resistances too high Is th...

Page 19: ...122 blind cover 161 back plate with axle 230 impeller 344 lantern 393 x thrust bearing part 401 housing gasket 415 1 centering gasket 509 1 intermediate ring 529 3 bearing sleeve 545 x bearing bush 55...

Page 20: ...nische nderungen vorbehalten Nicht ma st blich Ma e nur mit Unterschrift verbindlich CHEMIENORMPUMPEN CHEMICAL PROCESS PUMPS POMPE POUR L INDUSTRIE CHIMIQUE Baureihe Series S rie Ausf hrung Magnetkupp...

Page 21: ...igned Technische nderungen vorbehalten Nicht ma st blich Ma e nur mit Unterschrift verbindlich CHEMIENORMPUMPEN CHEMICAL PROCESS PUMPS POMPE POUR L INDUSTRIE CHIMIQUE Baureihe Series S rie Ausf hrung...

Page 22: ...st to the diagram shown the following admissible operating limits apply to the pump types MNK B 25 25 100 depending on the housing cover design Housing cover made of 1 4301 PFA 10 bar at 60 C to 150 C...

Page 23: ...1 Die technische Dokumentation nach Richtlinie 2014 34 EU ist bei der u a benannten Stelle hinterlegt The technical documentation is filed by below mentioned notified body according to directive 2014...

Page 24: ...nterne Fertigungskontrolle Production Quality Assurance Angewandte DIN EN ISO 12100 DIN EN 809 harmonisierte Normen DIN EN ISO 5199 ISO 15783 ISO 2858 Applied harmonised ASME B73 1 ASME B73 3 Standard...

Page 25: ...mination of the pumps valves and component sent in for repair On the basis of this information for the contractor is it possible to meet the necessary preventive action during the execution of the rep...

Page 26: ...logical 2 and with which cleaning method radioactive 3 1 if no then forward to D other pollutant 2 Aggregates which are contaminated with microbiological or explosive substances are only accepted with...

Page 27: ...rces Act WHG An inspection repair of Richter products and parts will only take place if the attached explanation is filled out correctly and completely by authorized and qualified technical personnel...

Reviews: