SCT Weight Transmitter – 20 Series Technical Manual
26
Visit our website
2.12 Setpoints Programming
1. Press
to enter setpoints and hysteresis settings.
2. Press or until desired setpoint or hysteresis parameter is displayed. Press
.
3. Press or until desired value is displayed. Press
.
4. Press
to exit setpoints and hysteresis settings.
Note
These values are set to zero if the calibration is changed significantly. See
Parameter
Options
Description
Full Scale
Setpoint; relay switching occurs when the weight exceed the
value set in this parameter. The type of switching is settable.
See
.
-Full Scale
Hysteresis, value to be subtracted from the setpoint to obtain
contact switching for decreasing weight. For example with a
setpoint at 100 and hysteresis at 10, the switching occurs at 90
for decreasing weight.
Table 2-17. Setpoints Parameters