RICE HYDRO FIRE HOSE TESTER Series Manual Download Page 1

RICE HYDRO, INC.

MANUFACTURER'S OPERATING INSTRUCTIONS

FIRE HOSE TESTER SERIES

FOR WARRANTY REGISTRATION CALL: 1-800-245-4777

CAUTIONS:

1.

Power source must meet voltage, phase, hertz and amperage requirements of 
electric motor, as stated on label.   If an extension cord is used, requires at 
least 12 gauge 3 wire with maximum of 25 foot length.

2.

Check ALL fluid levels prior to operating the unit.

3.

Protect the pump from freezing, FLUSH with anti-freeze.

4.

DO NOT run dry or pump chlorine thru the unit.

5.

Supplying the unit with water, inlet pressure should not exceed 90 PSI.

CONNECTING THE PUMP:

1.

Check oil level of pump and engine (if gas unit), use 10W30 ND oil.  

2.

Connect inlet to fire hydrant.

3.

Connect fire hose to be tested to suitable adapters on manifold outlets.  Hose 
should have nozzles on the end to bleed the air from the lines at full flow.  

4.

Connect garden hose to back bleed & direct to a drain away for dry test area.

5.

ASSURE MOTOR IS "OFF".  Connect the power cord to a standard wall outlet. 

Extension cord: when needed, a 12 gauge 3 wire, maximum 25 ft. length, plugged 
into a 20 amp breaker is required.

OPERATING THE PUMP:

1.

Close all ballvalves, slightly crack open the 1/2" bleeder ballvalve.

2.

Open inlet ballvalve.  Open outlet ballvalves one at a time and allow each hose 
to be filled through manifold.  Do not turn pump on at this time.

3.

To ensure air is safely bled from hoses, bleed each hose, one line at a time 
with hydrant volume and pressure, utilizing a nozzle at the end of each hose.

4.

When each line is filled, free of air, with nozzle closed, close the ballvalve 
at the manifold outlet to seal the line. Bleed 

ALL

 outlets whether or not in use 

for testing.  All air must be removed.

5.

With back bleed open, turn on the pump.  This will bleed air out of the pressure 
side of the pump - out to the drain area.

6.

Close the 1&1/2" ballvalve at the inlet of manifold/unit, directing water flow 
from the hydrant to pressure side of pump. No pressure will build until this 
ballvalve is closed.

7.

Slowly close the 1/2" back bleed ballvalve, check the gauge to verify pressure 
setting of relief valve.  

8.

The pressure regulator has been preset at the factory. 

To change this setting 

you must make this adjustment while the water is flowing freely, and under NO 
pressure. 

To adjust the pressure, first loosen the locknut. Turn the T-

handle/Knob clockwise to increase and counterclockwise to decrease the pressure. 
Place a ballvalve or similar open and close valve at the end of the outlet hose, 
open and close this valve multiple times as needed, to check pressure setting 
and re-adjust as necessary. Upon reaching desired pressure setting, tighten 
locknut and prepare to begin test.

Reviews: