SRV, SRD, SRV-FPC, SRD-FPC Installation and Intrinsic Safety Manual
P. 28
Version 2.0, Updated: October 29, 2020
Rheonics GmbH, Klosterstrasse 19, 8406 Winterthur, Switzerland
©Rheonics. Rheonics confidential and proprietary information.
1
Zener Barriers, safe area
2
Sensors, Zone 0
3
4 mm
2
bonding wires (1 per sensor)
4
4 mm
2
bonding wires (1 per sensor)
5
6 mm
2
wire connecting printing press ground point to barrier ground points
6
Common grounding points at printing press
7
Common grounding points at printing press
8
Star connected bonding
Figure 13: Several sensors grounded to
common grounding point (“Star” topology)
5.4.3.2.
Individual bonding conductors
A second method, which may be more convenient in situations when the safe zone is close to
the sensor installation area, is to use an individual bonding wire of at least 4mm
2
cross section
connecting each sensor to its associated Zener diode barriers. This is analogous to the use of
cable shields for bonding, except that the bonding conductors are now run parallel to the cables.
This arrangement is shown schematically in the following figure:
7
4
8
1
2
1
2
1
2
5