6.  CONTROLS

Inverter Models Only

The Display controls general operation. The layout, main 

functions and buttons are shown below.

HEATING

CAPACITY %

COMPRESSOR

HEATING

 

Figure 12.  Operation Display, Models -30-I through -65-I

Symbol

Designation

Button Functions

 

 

Press 3 seconds to unlock/lock 

screen

ON/OFF

Power On/Off

Speed

Smart/Silent Mode

Up

Temperature Adjustment

Down

Temperature Adjustment

Table E.  Display Button Functions

Power On

Press the LOCK button 

 

 for 3 seconds to light up screen, 

then press POWER 

 to power on the heater.

Adjust/Set Temperature: 

When screen is unlocked, press UP   or DOWN   to 

display or adjust the set temperature.
To change from Fahrenheit to Celsius, press the   and 

the   for 3 seconds.

Smart/Silent mode selection

Smart mode, as default, will be activated when the HEAT 

PUMP is on, and the screen shows 

.

Press FAN   to enter Silent Mode. The display screen 

will show  .

NOTE:

 Select Smart Mode for initial heating.

Screen Lock

If no button is used within 30 seconds, the screen will lock 

automatically. At this point the backlight will turn off and 0% 

will display.
Alternatively  you  can  lock  the  display  by  pressing  the 

LOCK button 

 

 for 3 seconds to achieve the same result.

To unlock the screen and use any other button, follow the 

Power On instruction above.

Defrosting

Auto Defrosting:

1.  When  the  heater  is  defrosting,  HEATING 

  will 

continually flash.

2.  After defrosting, HEATING 

 will stop flashing. 

Manual Defrosting:

1.  When heater is heating, press FAN 

 and MINUS 

 together for 5 seconds to start manual defrosting,  

 will flash continuously.

After defrosting, HEATING 

 will stop flashing.

NOTE:

 Manual defrosting intervals should be more than 

30  minutes  and  the  compressor  should  run  for  more 

than 10 minutes.

Heat, Cool or Auto Mode

1.  Press  the  Lock  button  for  3  seconds  to  light  the 

screen.

2.  Press  the  Lock  button  to  change  the  Heat  Pump 

operating MODE.

MODES:

•  POOL HEAT (sun icon) Heat to set point 
•  POOL COOL (snow icon) Cool to set point 
•  POOL AUTO (triangle icon) Heat or Cool to set point.

Summary of Contents for Raypak CROSSWIND-30-I

Page 1: ...anual are for the use of qualified individuals specially trained and experienced in the installation and maintenance of this type of equipment and related system com ponents Installation and service p...

Page 2: ...ou will be given a Warranty Registration Confirmation number which you should notate and keep in an easily remembered accessible location along with your Installation and Operation Manual a copy of yo...

Page 3: ...AGRAMS 14 Crosswind 30 I 50 I 14 Crosswind 40 I 15 Crosswind 65 I 16 Crosswind 40 O 17 Crosswind 50 O 18 Crosswind 65 O 19 6 CONTROLS 20 Inverter Models Only 20 On Off Models Only 21 Using the On Off...

Page 4: ...r is an electromechanical machine that incorporates a pressurized refrigerant gas in a sealed system ONLY trained and qualified service personnel are authorized to install or service this equipment Wi...

Page 5: ...before opening the case and performing service work 1 The heater must be installed by a qualified electrician 2 Set heating temperature within the recommended range to maximize comfort 3 Keep the air...

Page 6: ...mer weather Raypak recommends keeping the pool covered at night INSTALLATION Installation Considerations Locate the heater carefully to minimize installation costs while providing maximum efficiency o...

Page 7: ...ping it 3 Do not stack anything that will block air flow near the inlet or outlet areas or have any barrier within 20 508 mm behind the main heater or the efficiency of the heater will be reduced 4 Th...

Page 8: ...N CROSSWIND 30 I 17738 17742 17746 17750 CROSSWIND 40 I 17739 17743 17747 17751 CROSSWIND 50 I 17740 17744 17748 17752 CROSSWIND 65 I 17741 17745 17749 17753 On Off Models 60Hz Heating and Cooling Mod...

Page 9: ...ions Front View Figure 5 Inverter Model Component Locations Right Side View EVAPORATOR FAN COMPRESSOR HIGH AND LOW PRESSURE VALVE 4 WAY VALVE WATER FLOW SWITCH FRONT OF HEAT PUMP LED CONTROLLER LOW PR...

Page 10: ...4 25 9 657 106 48 CROSSWIND 50 I 12 4 315 23 2 312 12 3 312 13 4 340 39 991 13 330 2 9 74 25 9 657 115 52 CROSSWIND 65 I 15 6 395 23 2 312 15 4 390 16 5 420 39 991 14 2 360 2 9 74 25 9 657 137 62 On O...

Page 11: ...unit are 1 1 2 inch PVC unions Water connections from the heater to the main return line can be PVC pipe or flexible pipe approved for the purpose and in either case should be at least equal in size t...

Page 12: ...ENGINEER OR REGISTERED ARCHITECT SHALL PREPARE SITE SPECIFIC DOCUMENTS FOR USE IN CONJUNCTION WITH THIS DOCUMENT SITE SPECIFIC PRESSURE REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH ASCE 7 10 AND CHA...

Page 13: ...pre wired to work with external control systems heat on demand options and other external time clock overrides Refer to the external control system s instructions NOTE Please refer to page 23 for ins...

Page 14: ...14 5 WIRING DIAGRAMS Crosswind 30 I 50 I Touch Controller...

Page 15: ...15 Crosswind 40 I Touch Controller...

Page 16: ...16 Crosswind 65 I Touch Controller...

Page 17: ...17 LED Controller Automation Controller Crosswind 40 O...

Page 18: ...18 LED Controller Automation Controller Crosswind 50 O...

Page 19: ...19 LED Controller Automation Controller Crosswind 65 O...

Page 20: ...ct Smart Mode for initial heating Screen Lock If no button is used within 30 seconds the screen will lock automatically At this point the backlight will turn off and 0 will display Alternatively you c...

Page 21: ...ol models Setting pool water temperature Temperature can be adjusted either when the machine is on or off 1 Press UP or DOWN to set your target pool water temperature 2 The numbers on the LED screen w...

Page 22: ...ature settings for the pool or spa The temperature range is factory set from 64 F 18 C to 104 F 40 C HEAT ONLY 54 F 12 C to 86 F 30 C COOL ONLY Details on Inverter Models for starting and adjusting th...

Page 23: ...thinner or other flammable liquids Testing Inspection before use 1 Check installation of the entire heater and pipe connections according to the pipe connecting drawing 2 Check the electric wiring ac...

Page 24: ...ee Figure 18 5 To install the automation controller cable cut and splice the YELLOW jumper wire on Terminal PROT1 to the automation controller cable See Figure 19 6 Insert 36 1 meter of cable through...

Page 25: ...NG MULTIPLE HPPH with a LEAD HPPH to control the follower HPPH The program on the LEAD HPPH Followers needs to be change for the operation of the single HPPH to control the followers HPPH 1 Press and...

Page 26: ...t a failure Table H Fault Codes On Off Models Only No Display Non Failure Description 1 E3 No water protection 2 E5 Power supply excesses operation range 3 E6 Excessive temp difference between inlet a...

Page 27: ...7 C Humidity 63 Heating capacity BTUH 16 590 17 750 21 000 24 500 Heating capacity BTUH in silent mode 15 500 17 750 21 000 24 500 COP 4 0 4 0 4 16 4 10 Rated input power kW 1 15 1 26 1 28 1 55 Rated...

Page 28: ...ion Air 80 F 27 C Water 80 F 27 C Humidity 63 Heating capacity BTU 34 100 44 100 51 800 C O P 5 03 5 07 5 29 Performance Condition Air 50 F 10 C Water 80 F 27 C Humidity 63 Heating capacity BTU 20 500...

Page 29: ...18149F 241811 5 Inverter board 018150F 018155F 018155F 018155F 241812 6 Fan motor 018151F 018151F 018151F 018151F 241813 7 Fan blade 018152F 018152F 018152F 018152F 241814 8 Electronic expansion valve...

Page 30: ...tactor 018167F 018167F 018167F 241824 5 Compressor capacitor 018168F 018168F 018168F 241825 6 Fan motor 018169F 018169F 018177F 241813 7 Fan blade 018152F 018152F 018170F 241814 8 Fan motor capacitor...

Page 31: ...te of manufacture All Applicable Warranty Periods specified in this Limited Warranty are measured from the Effective Date APPLICABLE WARRANTY PERIOD UNREGISTERED If the Heater is installed with a pool...

Page 32: ...e Heater or component part and to verify warranty coverage at its factory Warranty service CANNOT be initiated until the status of the warranty coverage has been established EXCLUSIVE WARRANTY LIMITAT...

Page 33: ...33 NOTES...

Page 34: ...Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 www raypak com www raypak com...

Page 35: ...sont destin es des personnes qualifi es sp cialement form es et exp riment es dans l installation et l entretien de ce type d quipement et de ses composantes connexes Dans certaines r gions les techn...

Page 36: ...laire en ligne http warranty raypak com Nous vous fournirons un num ro de confirmation d enregistrement de garantie que vous devrez noter et conserver dans vos dossiers avec votre manuel N d enregistr...

Page 37: ...Crosswind 30 I 50 I 14 Crosswind 40 I 15 Crosswind 65 I 16 Crosswind 40 O 17 Crosswind 50 O 18 Crosswind 65 O 19 6 COMMANDES 20 Mod les vitesse variable seulement 20 Mod les une vitesse 21 Utilisatio...

Page 38: ...intes L immersion dans de l eau chauff e plus de 39 C 102 F peut causer des l sions foetales pendant les trois premiers mois de la grossesse comme des dommages c r braux ou des difformit s physiques 4...

Page 39: ...our supporter le poids de la tuyauterie externe Procurez un support suffisant la tuyauterie externe Coupez l alimentation lectrique avant d ouvrir le bo tier et d effectuer des travaux d entretien 1 L...

Page 40: ...dre la temp rature de consigne En certaines circonstances elle pourrait m me fonctionner jusqu 24 heures par jour et elle parfaitement con ue pour soutenir ce rythme M me lorsqu elle fonctionne pendan...

Page 41: ...tion suivante 2 Cet appareil n cessite un d gagement minimum de 305 mm 12 po des murs d arbustes d autre quipement etc sur le p rim tre entier de l appareil afin d viter d entraver l apport d air L am...

Page 42: ...CROSSWIND 30 I 17738 17742 17746 17750 CROSSWIND 40 I 17739 17743 17747 17751 CROSSWIND 50 I 17740 17744 17748 17752 CROSSWIND 65 I 17741 17745 17749 17753 Vitesse une vitesse 60 Hz chauffage et refr...

Page 43: ...DEL CAPTEUR DE SOUS PRESSURISATION CAPTEUR DE SUR PRESSURISATION CHANGEUR DE CHALEUR EN TITANE RACCORD D ENTR E 1 1 2 PVC MODULE DE COMMANDE DEL RACCORD DE SORTIE 1 1 2 PVC F10757 Figure 6 Mod le une...

Page 44: ...9 74 25 9 657 106 48 CROSSWIND 50 I 12 4 315 23 2 312 12 3 312 13 4 340 39 991 13 330 2 9 74 25 9 657 115 52 CROSSWIND 65 I 15 6 395 23 2 312 15 4 390 16 5 420 39 991 14 2 360 2 9 74 25 9 657 137 62...

Page 45: ...o Les raccords et conduites entre la thermopompe et la conduite de retour de la piscine peuvent tre en PVC ou en conduit flexible approuv pour cette application et leur diam tre doit tre au moins gal...

Page 46: ...ISTER AUX CHARGES COMBIN ES DOIT TRE V RIFI E PAR UN PROFESSIONNEL DE LA CONCEPTION ET N EST PAS INCLUSE LA PR SENTE CERTIFICATION SAUF INDICATION EXPRESSE AUCUNE CERTIFICATION SUPPL MENTAIRE N EST SP...

Page 47: ...tte thermopompe est con ue et pr c bl e en usine pour fonctionner avec un module de commande externe un module de chauffage la demande ou une minuterie Reportez vous aux instructions du syst me de con...

Page 48: ...Connecteur distant client Sonde entr e d eau Sonde sortie d eau Sonde changeur chauffage Sonde changeur refroidissement Sonde vacuation Sonde apport d air Sonde temp de l air Vanne d expansion lectron...

Page 49: ...actance 4 VOIES Connecteur distant client Sonde entr e d eau Sonde sortie d eau Sonde changeur chauffage Sonde changeur refroidissement Sonde vacuation Sonde apport d air Sonde temp de l air Vanne d e...

Page 50: ...eur distant client Sonde entr e d eau Sonde sortie d eau Sonde changeur chauffage Sonde changeur refroidissement Sonde vacuation Sonde apport d air Sonde temp de l air Capteur de sur pression Capteur...

Page 51: ...8 230V 60Hz Commande pompe Vanne d expansion lectronique Capteur de sur pression Capteur de sous pression D bitm tre R sistance fixe Sonde temp de l air Sonde changeur chauffage Sonde vacuation Sonde...

Page 52: ...ompe Contr leur d automatisation Module cran DEL Capteur de sur pression Capteur de sous pression D bitm tre R sistance fixe Sonde temp de l air Sonde changeur chauffage Sonde vacuation Sonde eau de p...

Page 53: ...ansformateur Vanne d expansion lectronique Contr leur d automatisation R sistance fixe Sonde temp de l air Sonde changeur chauffage Sonde vacuation Sonde eau de piscine Module cran DEL Capteur de sur...

Page 54: ...errouillage de l cran L cran se verrouille automatiquement lorsqu aucun bouton n est utilis en 30 secondes Le r tro clairage s teint et 0 s affiche Il est aussi possible de manuellement verrouiller l...

Page 55: ...z sur le bouton MODE pour passer d un mode un autre NOTE uniquement pour mod les refroidissement R glage de la temp rature La temp rature peut tre modifi e en tout temps thermopompe en marche ou l arr...

Page 56: ...module de commande permet d allumer ou d teindre la thermopompe et de r gler la temp rature de consigne La plage de valeur r gl e en usine est de 18 C 64 F 40 C 104 F CHAUFFAGE et de 12 C 54 F 30 C 86...

Page 57: ...l eau N utilisez jamais d essence de diluant peinture ou d autres liquides inflammables Test d installation Inspection avant utilisation 1 Assurez vous que les raccords et tuyaux sont install s comme...

Page 58: ...ps du bo tier lectrique Voir Figure 17 4 Rep rez le connecteur du CONTR LEUR D AUTOMATISATION Voir Figure 18 5 Pour installer le c ble de contr leur d automatisation couper et pisser le fil cavalier J...

Page 59: ...e consigne des APPAREILS SECONDAIRES doit tre r gl 40 C 104 F a Appuyez sur les boutons LOCK et HOLD pendant 3 secondes pour allumer l cran b Alors que l cran est d verrouill appuyez sur le bouton pou...

Page 60: ...UR clignote D givrage en cours pas une panne Table H Codes d erreur Mod les une vitesse seulement N Afficheur Description d tat 1 E3 Protection manque d eau 2 E5 Suralimentation lectrique 3 E6 cart de...

Page 61: ...humidit 63 Capacit de chauffage BTU h 16 590 17 750 21 000 24 500 Puissance de chauffage BTU H en mode silencieux 15 500 17 750 21 000 24 500 Coefficient de performance 4 0 4 0 4 16 4 10 Puissance d e...

Page 62: ...80 F eau 27 C 80 F humidit 63 Capacit de chauffage BTU h 34 100 44 100 51 800 Coefficient de performance 5 03 5 07 5 29 Conditions m t o Air 10 C 50 F eau 27 C 80 F humidit 63 Capacit de chauffage BT...

Page 63: ...149F 241811 5 Carte de l onduleur 018150F 018155F 018155F 018155F 241812 6 Moteur ventilateur 018151F 018151F 018151F 018151F 241813 7 Pales ventilateur 018152F 018152F 018152F 018152F 241814 8 Vanne...

Page 64: ...018167F 018167F 241824 5 Condensateur du compresseur 018168F 018168F 018168F 241825 6 Moteur ventilateur 018169F 018169F 018177F 241813 7 Pales ventilateur 018152F 018152F 018170F 241814 8 Condensateu...

Page 65: ...ment autoris avec la piscine ou le spa d une habitation unifamiliale avec le re u d installation joint l enregistrement et enregistr aupr s de Raypak www raypak com dans les quatre vingt dix 90 jours...

Page 66: ...modifi par TOUTE AUTRE PERSONNE OU ENTREPRISE que celles autoris es par Raypak Raypak se r serve en tout temps le droit d inspecter la thermopompe ou d exiger son retour ou celui du composant d fectu...

Page 67: ...33 NOTES...

Page 68: ...Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 www raypak com www raypak com...

Reviews: