7.10.7
Changed Setting Parameter by Load CytroPac Configuration
Code
Name
Setting range
Default
Min.
Attri.
F1.20
CytroPac parameter initialization
0: No selection
1: CytroPac basic
2: CytroPac advanced
3: CytroPac ad
comm.
0
-
Stop
Tab. 7-43:
Auto-modified FcP 5020 parameter list in CytroPac initialization
When CytroPac parameter is initialized (via F1.20), all F group parameters
and some EFC parameters will be changed to CytronPac default settings ac‐
cording to diverse CytroPac variants. The CytroPac default settings are differ‐
ent from FcP default setting by following parameters shown in the list:
Code
Name
FcP default
setting
CytroPac
basic
CytroPac
advanced
CytroPac
ad
comm.
E0.17 Direction control
3
1
1
1
E1.61 Broken wire protec‐
tion
0
2
2
2
E2.15 Relay1 output selec‐
tion
14
15
15
15
F1.03 Pressure command
source
0
- *
-
3
F1.11 Flow
command
source
0
-
-
2
F1.15 Motor type
1
0
0
0
F2.18 X3 input
0
-
16
16
F2.19 X4 input
0
-
15
15
F2.20 X5 input
0
-
7
7
F2.21 EX1 input
0
-
6
6
F2.22 EX2 input
0
-
8
8
F2.23 EX3 input
0
-
1
-
F2.24 EX4 input
0
-
2
-
F2.36 DO1 output
1
0
2
2
F2.37 EDO output
0
-
3
3
F3.00 p/Q parameter se‐
lection source
0
-
-
2
F4.00 Protection function
control word
0
8
8
8
F4.36 Pump thermal pro‐
tection speed
500
0
0
0
Tab. 7-44:
Different parameter list between CytroPac and FcP default setting
* Not changing current value of this parameter.
DOK-SYTROX-FCP5020****-IT01-EN-P
Bosch Rexroth AG
141/201
Frequency-controlled pump drive system Sytronix FcP 5020
Commissioning of Sytronix FcP 5020 System