7.10.5
Group F4: System Protection and Pump Function Parameter
Code
Name
Setting range
Default
Min.
Attri.
F4.00 Protection function configuration word
0...15
Bit0: Pressure sensor failure (PSF)
Bit1: Actual pressure monitoring
Bit2: p/Q max. command limit
Bit 3: Oil changing detection
0
-
Run
F4.03 Pump function configuration word
0...63
Bit0: Pump power limit
Bit1: Pump thermal protection
Bit2: Switch master to slave
Bit3: Two points / double pump
Bit4: Pressure drop / overshoot
compensation
Bit5: Activating myCro
0
-
Stop
F4.06 Pressure sensor failure detection thresh‐
old 1 (negative direction)
-5,000...0 rpm
-1
1
Stop
F4.07 Pressure sensor failure detection time 1
(negative direction)
0.1...100.0 s
10.0
0.1
Stop
F4.08 Pressure sensor failure detection thresh‐
old 2 (positive direction)
0...5,000 rpm
200
1
Stop
F4.09 Pressure sensor failure detection time 2
(positive direction)
0.1...100.0 s
10.0
0.1
Stop
F4.10 Pressure sensor detection threshold
(standby)
1.0...1,000.0 bar
5.0
0.1
Stop
F4.11 Pressure sensor detection period
(standby)
0.1...100.0 s
1.0
0.1
Stop
F4.15 Maximum system pressure (warning)
0.0...[F4.16] bar
500.0
0.1
Stop
F4.16 Maximum pump pressure (error)
[F4.15]...4,000.0 bar
1,000.0
0.1
Stop
F4.17 Maximum system pressure warning time
delay
0.0...6000.0 s
0.0
0.1
Run
F4.18 Maximum pump pressure error time de‐
lay
0.0...6000.0 s
0.0
0.1
Run
F4.20 p/Q command soft start delay
0.0...1,000.0 s
0.0
0.1
Stop
F4.21 Minimum pressure command limit
0.0...[F4.22] bar
5.0
0.1
Stop
F4.22 Maximum pressure command limit
[F4.21]...1,000.0 bar
250.0
0.1
Stop
F4.23 Minimum flow command limit
0...[F4.24] rpm
200
1
Stop
F4.24 Maximum flow command limit
[F4.23]...5,000 rpm
3,000
1
Stop
F4.25 Acceleration time hydraulic soft start
0.1...6,000.0 s
5.0
0.1
Run
F4.28 Two points / double pump selection
0: Two points pump
1: Double pump
0
-
Stop
Bosch Rexroth AG
DOK-SYTROX-FCP5020****-IT01-EN-P
138/201
Frequency-controlled pump drive system Sytronix FcP 5020
Commissioning of Sytronix FcP 5020 System