7.10.4
Group F3: p/Q PID Parameter
Code
Name
Setting range
Default
Min.
Attri.
F3.00 p/Q parameter selection source
0: Depend on the value of F3.01
1: Digital input
2: Communication
0
-
Stop
F3.01 p/Q parameter digital selection
0: Parameter group 0
1: Parameter group 1
0
-
Run
F3.02 Filter time for pressure feedback
0...999 ms
4
1
Run
F3.03 Filter time for flow command
0...999 ms
4
1
Run
F3.10 Filter time for pressure ascending [0]
0...999 ms
80
1
Run
F3.11 Filter time for pressure descending [0]
0...999 ms
40
1
Run
F3.12 Proportional gain [0]
0.00...500.00 rpm/bar
8.00
0.01
Run
F3.13 Integral time 1 [0]
0...999 ms
80
1
Run
F3.14 Integral time 2 [0]
0...999 ms
0
1
Run
F3.15 Integral time TI switch threshold [0]
-150.0...0.0 bar (set to 0.0, the switching
function is invalid)
0.0
0.1
Run
F3.16 Differential gain [0]
0.000...10.000 (rpm/bar)*s
0.000
0.001
Run
F3.17 Filter time for Kd [0]
0...999 ms
35
1
Run
F3.18 Lower limit for I+D [0]
-5,000...5,000 rpm
0
1
Run
F3.19 System minimum speed [0]
-5,000...5,000 rpm
0
1
Run
F3.30 Filter time for pressure ascending [1]
0...999 ms
80
1
Run
F3.31 Filter time for pressure descending [1]
0...999 ms
40
1
Run
F3.32 Proportional gain [1]
0.00...500.00 rpm/bar
8.00
0.01
Run
F3.33 Integral time 1 [1]
0...999 ms
80
1
Run
F3.34 Integral time 2 [1]
0...999 ms
0
1
Run
F3.35 Integral time TI switch threshold [1]
-150.0...0.0 bar (set to 0.0, the switching
function is invalid)
0.0
0.1
Run
F3.36 Differential gain [1]
0.000...10.000 (rpm/bar)*s
0.000
0.001
Run
F3.37 Filter time for Kd [1]
0...999 ms
35
1
Run
F3.38 Lower limit for I+D [1]
-5,000...5,000 rpm
0
1
Run
F3.39 System minimum speed [1]
-5,000...5,000 rpm
0
1
Run
F3.40 Pressure command arrived threshold
0.1...1,000.0 bar
5.0
0.1
Run
Tab. 7-40:
Parameter list of group F3
DOK-SYTROX-FCP5020****-IT01-EN-P
Bosch Rexroth AG
137/201
Frequency-controlled pump drive system Sytronix FcP 5020
Commissioning of Sytronix FcP 5020 System