7.5.6
Pressure and Flow Command Limit
Code
Name
Setting range
Default
Min.
Attri.
F4.00
Protection function control word
0...15
Bit0: Pressure sensor failure (PSF)
Bit1: Actual pressure monitoring
Bit2: p/Q max. command limit
Bit3: Oil changing detection
0
-
Run
F4.21
Minimum pressure command
limit
0.0...[F4.22] bar
5.0
0.1
Stop
F4.22
Maximum pressure command
limit
[F4.21]...1,000.0 bar
250.0
0.1
Stop
F4.23
Minimum flow command limit
0...[F4.24] rpm
200
1
Stop
F4.24
Maximum flow command limit
[F4.23]...5,000 rpm
3,000
1
Stop
Tab. 7-26:
Parameter list of pressure and flow command limit
The minimum pressure and flow command limitation (F4.21 and F4.23) works
all the time, independently to any control bit. That means if the setting pres‐
sure or flow command is lower than [F4.21] or [F4.23], it will be limited to
[F4.21] or [F4.23] without any error / warning message.
The maximum pressure and flow command limitation can be activated via
bit2 of F4.00. This function will check whether the pressure or flow command
given by customer exceeds the limitation set in [F4.22] and [F4.24]. If a given
command exceeds its limitation, the effective command value will be limited
to the maximum limit, and a warning signal will be raised.
Bosch Rexroth AG
DOK-SYTROX-FCP5020****-IT01-EN-P
114/201
Frequency-controlled pump drive system Sytronix FcP 5020
Commissioning of Sytronix FcP 5020 System