RD 500 RD51
Parameter Value Assignment
8-15
DOK-RD500*RD51*******-IB04-EN-P
Functions
•
Controller
setting
•
Start / stop function
•
Thermal motor protection
•
V / Hz control (open loop)
Controller setting
Para-
meter
No.:
Name
Description / explanation
selectable options
Factory setting
min ... max values
Pass-
word
0547.00
Current control Kp
0.10
1
Current controller gain factor.
0.01 ... 128.00
0548.00
Current control Tn
10 ms
1
Current controller integral action time.
0 ... 5000 ms
0532.00
Fixv., current limit
100.00 %
1
Enters the current limit
100 % corresponds to the contents of parameter
P0374 (factory setting: Continuous output current of
the drive).
0.00 ... 190.00 %
0574.00
Curr. limit timeout
0
1
Selects Current limit
0 = continuous
1 = 1 second
2 = 2 seconds
3 = 4 seconds
4 = 6 seconds
5 = 8 seconds
6 = 10 seconds
7 = 20 seconds
8 = 40 seconds
9 = 60 seconds
10 = 80 seconds
11 = 100 seconds
Start- / stop functions
Para-
meter
No.:
Name
Description / explanation
selectable options
Factory setting
min ... max values
Pass-
word
0544.00
Delay after start
0.3 sec
1
After the start, the delay time fa (P0181) is entered
after which, the drive accelerates to the selected
setpoint.
0.0 ... 100.0 sec
0539
High inertia start
No
2
For the first run-up after start, twice the current
limiting is enabled.
0 = no 1 = yes
0 / 1
0043
Inhibit operation
Coast-down
2
0 = braking 1 = coast-down
0 / 1
0044
Inhibit drive
Coast-down
2
0 =braking 1=coast-down
0 / 1
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......