RD 500 RD51
Operator Control and Visualization
7-7
DOK-RD500*RD51*******-IB04-EN-P
Monitor Functions
Four selectable parameters are simultaneously displayed. The parameter
monitor can be used to support commissioning, e.g. the speed setpoint
route can be tracked using the parameterizable functions of the converter.
In this case, use the D parameters from the function charts.
The last 10 faults are saved in the fault memory. The most recent fault is
in memory location S0, the oldest in S9. A new fault is always saved in
memory location S0. All of the older faults are always shifted one position
upwards in the memory. This means the fault in memory location S9 is
lost.
The existing V/f (V / Hz) characteristic is graphically displayed in this
menu.
Faults and irregularities which occur when copying a data set from the
operator field in the converter are displayed in this menu. The copy status
is lost when the drive converter is shut down.
A list of “Parameter sources” in which the selected D parameter is
connected is displayed using “Search for D parameters”. The list can be
scrolled using the Enter key. If the selected D parameter is not linked with
a “Parameter source”, the following is displayed: “is not linked”. Refer to
the function charts with legend for additional information on this subject.
Operating Display
From ten display values, three can be selected to be displayed in the
operating display; refer to P0037.0x.
fact
0.00Hz
fset
0.00Hz
operation
0
Line 1: Frequency actual value
Line 2: Frequency setpoint
Line 3: Status (operating status)
Active parameter
FA510001EN00.FH9
Active parameter in normal operation. The system changes-over into the test
mode when the (
<
) and (
>
) key are simultaneously pressed. “0T” is
then displayed.
Fig.: 7-10
Operating display
Warning Display
If a critical operating condition develops, a warning message and
operating display are displayed alternatingly until this critical condition has
been resolved.
FA510002EN00.FH9
fact
0.00Hz
fset
0.0 Hz
operation
0
Warning
Motor overtemp.
Fig.: 7-11
Warning display
Parameter
Fault memory
Graphic display
Copy status
Search for D parameters
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......