![REXROTH RD 500 Series Applications Manual Download Page 146](http://html1.mh-extra.com/html/rexroth/rd-500-series/rd-500-series_applications-manual_1449588146.webp)
5-6
Inverter Technical Data
RD 500 RD51
DOK-RD500*RD51*******-IB04-EN-P
5.6
Technical Data for Size Classes G with Pulse Frequency f
p
= 4 kHz / 8kHz
4 kHz
8 kHz
RD51.1
132
160
200
132
160
200
Rated motor output
1)
kW
132
160
200
110
132
160
Supply voltage DC 530 ... 670 V (±10 %)
2)
Output frequency
3)
Hz
0 - 250
0 - 150
0 - 500
0 - 250
Rated current
A 230
290
350
195
230
280
Peak current for t = 60 s A
299
377
455
254
299
364
t = 1 s A
391
493
595
332
391
476
Rated output S
N
kVA 151
191
230
128
151
184
Peak power for t = 60 s kVA 197
248
299
166
197
240
Supply voltage DC 700 V (±10 %)
Output frequency
3)
Hz
0 - 250
0 - 150
0 - 500
0 - 250
Rated current
A 190
240
280
160
190
240
Peak current for t = 60 s A 247
312
364
208
247
312
t = 1 s A
323
408
476
272
323
408
Rated output S
N
kVA 156
197
230
132
156
197
Peak power for t = 60 s kVA 203
257
299
171
203
257
Ambient conditions, noise suppression level, interference immunity
Environmental class
3K3 according to DIN IEC 721-3-3 (ambient temperature 0 – 40 °C operation,
to 50 °C power reduction at 2.5 % per K)
Cooling air requirement
m³ / s
0.4
0.4
0.6
0.4
0.4
0.6
Power loss kW 5.2
6.5
7.7
4.4
5.2
6.5
Radio int. sup. level / noise immunity
A 1 according to EN 55011 / EN 61800-3
Mechanical design
Size classes
G
G
G
G
G
G
Degree of protection
IP 20 according to EN 60529 (without connection terminals)
Weight of inverter for the various cooling types
F Forced air cooling with integrated
liquid circuit kg 128
128
128
128
128
128
R Liquid cooling with
internal pump kg 105
105
105
105
105
105
1):
Max. permissible motor power based on 4-pin standard induction
motor
2):
Starting at an output voltage Ua >400 V, the rated current is linearly
reduced from 100 % to 83 % for Va = 480 V.
3):
If Output frequency >150 Hz the additional function M1 is required
(without integrate Motor filter)
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......