RD 500 RD51
Electrical Installation of Converter
4-45
DOK-RD500*RD51*******-IB04-EN-P
Interconnection with other
Converters or SPS
RD51 / RD52 / RS51 / RD41 / RD42
ST520016EN01.FH9
RD500
RD500
0V
SPS
0V
24V
-
+
24V
0V
PE
0V
X14.7
X11.14
RD51.x
RD52.x
RS51
RD41
RD42
X11.15
n.c.
Fig.:4-12
Central Connection reference ground to PE
If there is no potential control connection between the devices (e.g.
coupling using fiber optic cabler), the reference ground is directly
connected to the PE on each device.
Note:
When delivered, RD 500 devices have a direct connection
between the reference ground and the PE via the X14.7 cable
connection to the housing (RD51, RS51, RD52) or via jumper
X11.14 / 15 (RD41, RD42).
RDxx
X14.7
0V-Elektronik
PE-Lug
Stand alone
or
Interconnection with floating SPS
RD51 / RD52 / RS51
ST520017EN01.FH9
Fig.:4-13
Central connection between reference ground PE in RD51, RS51
and RD52
Incremental encoder connection
Terminal strip X17 has a double function. When the equipment is
supplied, the terminals are used as digital inputs. This can be changed-
over to connect an HTL incremental encoder using parameter P0130
(encoder selection).