![REXROTH RD 500 Series Applications Manual Download Page 113](http://html1.mh-extra.com/html/rexroth/rd-500-series/rd-500-series_applications-manual_1449588113.webp)
RD 500 RD51
Electrical Installation of Converter
4-25
DOK-RD500*RD51*******-IB04-EN-P
Description of Power Terminals, Converter Size Classes G - H
X1, Line supply connection
RD51.1-x- Type
number
Execution
132
High current terminal
3
Terminal on mounting rail
160
High current terminal
3
Terminal on mounting rail
200
High current terminal
3
Terminal on mounting rail
315
Stud connection
3
rail
400
Stud connection
3
rail
Tab. 4-48
Execution
Identification single connection
Identification signification
U1
Phase L1
V1
Phase L2
W1
Phase L3
for permissible line supply voltage, refer to
the rating plate on the upper side of the drive
unit
Tab. 4-49
Identification single connection
•
terminal rail with cable clamp size G (stud M8 torque 12.0 Nm)
•
with M16 and M12 screws size H (torque 120.0 Nm, 50Nm)
RD51.1-x-
Cable cross-
section which can be
connected 1), mm²
AWG
Torque
in Nm
132
50 – 100
1/0 – 300MCM
25 - 30
160
50 – 100
1/0 – 300MCM
25 - 30
200
50 – 100
1/0 – 300MCM
25 - 30
315
M16
120
400
M16
120
1):
As a result of the terminal size
Tab. 4-50
Connection cross-section
See table.
Execution
Protective conductor connection
Connection cross-section
Torque
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......