RD 500 RD51
Electrical Installation of Converter
4-23
DOK-RD500*RD51*******-IB04-EN-P
4.5
Power Terminals RD51 Size Classes G - H
After the device has been mounted, the electrical connections between
the line filter and drive converter must be established:
•
Bolt the busbars provided between the main contactor of the line filter
and the converter.
•
Insert the assembled cable with connector (coming from the line filter)
into terminal strip X5 in the converter.
•
Depending on the line supply voltage, check whether the settings on
the control transformer are correct. (See Example Control
transformer page 4-37).
Terminal Layout Diagram Converter Size Class G
U1V1W1
Heat exchanger
Converter
Line filter
X80
Starting lock-out
X5
Connection to Line filter
X2
DC link, brake resistor
control voltage
X2
Motor connection
terminal for additional function
(L1, F1, W1, Z1)
T1
Control transformer
busbars between Line contactor and converter
K1
Main conductor
X1
Line connection
PE
Terminal rail for Protective conducter
Screen connection for Motor cable
busbars for strain relief
X1
Feedback Main contactor
U2 V2 W2
Feedback Pre-charging contactor
AN520004EN03.FH9
ALARM
ON
READY
ESC
START
STOP
MON
ENTER
PROG
-
+
X83 24 V - Power supply
C D
F
12
1 2
1 2 4 5
1 ................15
Fig.: 4-4
Terminal layout diagram, converter size class G
Summary of Contents for RD 500 Series
Page 32: ...2 12 Description of RD51 RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 174: ...5 34 Inverter Technical Data RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 248: ...9 4 Commissioning RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 274: ...14 6 Index RD 500 RD51 DOK RD500 RD51 IB04 EN P...
Page 275: ......