Rexroth IndraDrive FCS01.1
Indications and Operation of the Function Modules
9-19
DOK-INDRV*--FCS01*****-IB01_EN-P
Error Messages Comfort Control Panel
Indication
Failure
Cause
•
Remedy
Error in the communication system
200
INVALID PARAMETER
NUMBER
201
PARAMETER VALUE
CANNOT BE
CHANGED
202
PARAMETER OUTSIDE
OF VALUE RANGE
203
INCORRECT SUB-
INDEX
204
NO ARRAY
PARAMETER
205
INCORRECT
PARAMETER TYPE
206
INCORRECT REPLAY
ID USS INTERFACE
These error messages are based on EMC malfunctions or different software versions of the
nodes.
•
Check the software version of the comfort control panel and that of the connected
frequency converter.
•
Check the wiring of all components for EMC faults.
207
CHECKSUMS
ERROR OF THEUSS
INTERFACE
The communication between the frequency converter and the comfort control panel is faulty
(EMC). Safe operation cannot be guaranteed.
•
Check the comfort control panel for correct connection to the FC.
208
INCORRECT STATUS
ID
USS INTERFACE
The communication between the frequency converter and the comfort control panel is faulty
(EMC). Safe operation cannot be guaranteed.
•
Check the comfort control panel for correct connection to the FC.
209_1
CONVERTER DOES
NOT REPLY
The comfort control panel is waiting for the connected frequency converter to reply. The
waiting period has passed without receipt of a reply.
•
Check the comfort control panel for correct connection to the FC.
Summary of Contents for IndraDrive Fc FCS01
Page 28: ...5 2 Delivery Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 34: ...6 6 Certifications and Types Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 56: ...8 20 Installation Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 88: ...10 4 Commissioning Rexroth IndraDrive FCS01 1 DOK INDRV FCS01 IB01_EN P ...
Page 237: ......