![REXROTH HCS02.1 Series Project Planning Manual Download Page 75](http://html1.mh-extra.com/html/rexroth/hcs02-1-series/hcs02-1-series_project-planning-manual_1449567075.webp)
Rexroth IndraDrive C
Electrical Data
6-35
DOK-INDRV*-HCS02.1****-PR02-EN-P
X9, Connection of Braking Resistor
DANGER
Lethal electric shock caused by live parts with
more than 50 V!
⇒
Exclusively operate the drive controller with plugged
on connector!
HCS02.1E-
Type
Number of poles
Type of design
W0054
Terminal screw
2
Pins on device
W0070
Terminal screw
2
Pins on device
Fig. 6-41:
Design
Identification of the individual connections:
Identification
Significance
1
phase 1
2
phase 2
Fig. 6-42:
Identification of the individual connections
HCS02.1E-
Cross section
single-wire
[mm²]
Cross section
multi-wire
[mm²]
Cross section
in AWG
W0054
0.5-10
0.5-10
20-8
W0070
0.5-10
0.5-10
20-8
Fig. 6-43: Connection cross sections
HCS02.1E-
Tightening torque [Nm]
W0054
1.2 – 1.5
W0070
1.2 – 1.5
Fig. 6-44: Tightening torque
CAUTION
Damage to the drive controller!
⇒
You have to provide strain relief for the connection
cable in the control cabinet or use the optionally
available connection accessory (shielding plate;
HAS02.1).
Maximum allowed current load
I
max
= 30 A
I
eff
= 15 A
short circuit protection
via fusing of devices
Fig. 6-45:
Load capacity
Design
Connection Cross Section
Tightening Torque
Load Capacity