6-28
Electrical Data
Rexroth IndraDrive C
DOK-INDRV*-HCS02.1****-PR02-EN-P
X3, Mains Connection
DANGER
High electrical voltage! Danger to life, severe
bodily harm by electric shock!
⇒
Always operate the drive controller with plugged on
connector!
HCS02.1E-
Type
Number of
poles
Type of design
W0012
Terminal screw
4
Pins on device
W0028
Terminal screw
4
Pins on device
W0054
Terminal screw
4
Pins on device
W0070
Terminal screw
4
Pins on device
Fig. 6-29:
Design
Identification of the individual connections:
Identification
Significance
L1
phase 1
L2
phase 2
L3
phase 3
equipment grounding conductor
Fig. 6-30:
Identification of the individual connections
Note:
Only with single-phase operation: connect the connecting lines
of the mains voltage supply L1 and N with the connections L1
and L2.
HCS02.1E-
Cross section
single-wire
[mm²]
Cross section
multi-wire
[mm²]
Cross section
in AWG
W0012
0.2-4
0.2-4
24-10
W0028
0.2-4
0.2-4
24-10
W0054
0.5-10
0.5-10
20-8
W0070
0.5-10
0.5-10
20-8
Fig. 6-31: Connection cross section
HCS02.1E-
Tightening torque [Nm]
W0012
0.5 – 0.6
W0028
0.5 – 0.6
W0054
1.2 – 1.5
W0070
1.2 – 1.5
Fig. 6-32: Tightening torque
Design
Connection Cross Section
Tightening Torque