12.1.2 Parameter Initialization
This function is used to restore parameter settings to factory defaults when a
frequency converter fails to drive the motor due to wrong parameter settings.
Be sure that the parameter settings match with the motor data and the actual
applications after factory defaults restore. Adjust the parameter default settings
if necessary.
Code
Name
Setting range
Default
Min.
Attri.
b0.09 Parameter initialization
setting
1: Base device and non fieldbus op-
tions
2: Fieldbus options
3: Base device, non fieldbus and field-
bus options
1
–
Stop
Parameters will be restored to factory default based on the setting of b0.09:
●
b0.09 = 1: b0, d0, C0, C1, C2, C3, E0, E1, E2, E3, E4, E5, E8, E9, H0, H8, H9,
U0, U1, U2, F0, ASF related parameters
●
b0.09 = 2: H1, H2, H3
●
b0.09 = 3: All parameters are restored to factory default
Code
Name
Setting range
Default
Min.
Attri.
b0.10 Parameter initialization
0...2
0
–
Stop
●
0: Inactive
This parameter will be reset to '0: Inactive' automatically after parameter initi-
alization.
●
1: Restore to default settings
All parameters are restored to factory default settings except for:
– C0.51 (Fan total running time)
– E9.05…E9.07, E9.10…E9.15, E9.97...E9.99 (Error records)
– d0.23 (Power stage running time)
●
2: Clear error record
Parameter E9.05… E9.07, E9.10…E9.15, E9.97...E9.99 (Error records) will be
cleared.
●
b0.09 is available from firmware version 03V08.
●
E9.97...E9.99 are available from firmware version 03V10.