11.3 Control the Motor
WARNING
Ensure the enclosure is in place before the device is powered on. Wait for at
least 5 minutes after powering off to allow the DC capacitor being discharged,
and do not remove the cover during this period!
Step
Operation
Description
1
Rotate the potentiometer counterclockwise
(leftwards) to the greatest extent
Output frequency setting is 0.00
2
Press <Run> button
Control command active, 0.00 is displayed
3
Rotate the potentiometer clockwise (right-
wards) slowly till 5.00 is displayed
The motor starts to run
Observe the running status:
If the motor runs in the correct direction
If the motor runs steadily
If there is any abnormal noise or problem
Recommended operation:
Stop the motor immediately by switching off
the power if any abnormality occurs
Restart commissioning only after error cau-
ses have been removed
4
Rotate the potentiometer clockwise
The motor accelerates
5
Rotate the potentiometer counterclockwise The motor decelerates
6
Press <Stop> button
Stop command activated, the motor stops
7
Check parameters without load
Settings according to actual applications
8
Check parameters with load
Settings according to actual applications
Tab. 11-5: Motor controlling procedure
●
After powering on, EFC x610 will generate output if pressing down the <Run>
button (or 'Control by terminals' is activated).
●
By default, EFC x610 is set as:
– The frequency converter is started or stopped by the operating panel.
– The output frequency is set by the potentiometer on the operating panel.
●
After powering on, please confirm:
– The setting frequency is displayed (no error display).
– The monitoring parameter is consistent with the actual situations.
●
By default, Output frequency in run status and Setting frequency in stop sta-
tus are displayed as the monitoring parameters, which can be changed to oth-
er parameters with parameters U1.00 and U1.10. The default settings are
based on standard applications with standard motors.
For frequency converters with dust cover, it is recommended to in-
stall an LED panel to perform the above operations.