ECODRIVE03 Drive Controllers
Replacing or Exchanging Drive Components
15-9
15.4 Replacing Firmware (DKC**.3-016-7-FW)
•
Secure parameters (DriveTop)
•
Set Parameter
P-0-4021, Baud-Rate RS-232/485
to 0 (Baud rate
9600)
•
Close DriveTop
•
Start DOLFI
•
Press Button "Connect"
•
Open IBF-file of the fimware by pressing button "Open file"
•
Transfer the three files of the IBF-file by pressing button "Transfer file"
and confirm the transfers.
•
In event of download problems you have to reduce the Baud rate (see
menu item "Settings"; see also help system of DOLFI)
•
Restart the drive with "Serial disconnecting"
•
Load parameters (DriveTop)
|