441/451 Commercial DucTester QuickGuide

Prepare the gauge, first time only

1

Home

 screen must show Model 450 on 

Range 47. 

If not, tap the device icon, then
Tap       until “Retrotec DucTester” appears. 

Tap               then tap 

 www.retrotec.com       Support:  (888)330-1345     International:  +1(604)732-0142         Made in Everson, WA, USA

Page 1

DucTester

Flex

Channel A

Channel B

Umbilical

Extra tubing

Range plugs

DM32 20A gauge

Gauge case

System case

Battery Charger

Tubing 

Accessory Kit

QuickGuides

Change 

Device

...

If units on Channel A and B are NOT correct

If time average is NOT “5 s avg”

- Tap 

[Settings]

 > 

[Results to be displayed]

- Tap 

[Pressure:]

 to change pressure

- Tap 

[Flow:]

 or 

[Flow/Area] 

to change flow

   units

- Tap        to return 

Home

.

- Tap 

[Settings] 

[Time Averaging]

 “5 seconds”

- Tap        to return Home.

Summary of Contents for 441

Page 1: ...142 Made in Everson WA USA Page 1 DucTester Flex Channel A Channel B Umbilical Extra tubing Range plugs DM32 20A gauge Gauge case System case Battery Charger Tubing Accessory Kit QuickGuides Change Device If units on Channel A and B are NOT correct If time average is NOT 5 s avg Tap Settings Results to be displayed Tap Pressure to change pressure Tap Flow or Flow Area to change flow units Tap to r...

Page 2: ...ug in the Speed Control Cable between DucTester and Gauge Install Range 47 Flow Plug Attach 4 inch 100 mm Flex to ductwork Connect Flex Duct to fan outlet for pressurization On Model 451 you can depressurize ducts by attaching the Adapter onto Fan inlet and attaching the Flex to it 47 Inlet with Range Plugs airflow Outlet airflow Inlet with Flow Plugs Flex duct adapter Flex connects here Page 2 i ...

Page 3: ... in to power source Set Speed to 1 then Jog up to the Test Pressure Tap on the display and Flow at Test Pressure or Flow Area at Test Pressure will appear Jog fan speed up but do not exceed the Pressure Class Read results from the Gauge Tap Settings Default Pressure and enter Test Pressure Tap to return Home If your flow units include area tap Area then use number pad to enter the area and tap Set...

Page 4: ...ange Range to match Re adjust fan speed Change to a higher Range Plug and try again Change Range on the gauge to match Check seals on all registers Look for disconnected ducts or ducts open to outdoors Set Time Average to 5 seconds in Settings Tap Channel B and select Pressure Pa Connect the yellow tube between the red and yellow ports Check gauge operation and check for blocked leaking or pinched...

Reviews: