RE112_GE-Compat_Smoke_Instructions
Page 1 of 3
29-Oct-14
24-Hour Tech Support Line: (715)808-0164
www.ResolutionProducts.com
RE112 GE-Compatible Smoke & Heat Alarm
Features
•
UL217 Self-Contained Fire Alarm Device
•
Senses and alarms to Smoke per UL217
•
Heat alarm at 144 degrees.
•
Sleek design.
•
Cover tamper.
•
Strong, reliable RF signal.
•
3-5 year battery life on Panasonic CR123A battery.
•
Low Battery indication.
Key Instructions
1.
Attach the mounting plate
Locate on ceiling, as close to center as possible, away from corners.
Some local codes may allow wall mounting.
Mounting plate removes counter-clockwise
2.
Insert battery with MINUS towards the RED lever. Close battery door.
3.
Enroll sensor in panel:
a)
Place panel in Learn Sensor mode
b)
Press & release the black tamper switch
Sounder will continue beeping 3 times, until sensor is mounted.
c)
Recommended GE Group # (26)
4.
Testing:
a) Place panel in Sensor Test mode
b) Press & hold TEST button until you hear the sounder beep.
d)
Panel will indicate the sensor is open, but Fire Alarm will not sound.
NOTE: Using Smoke-in-a-Can will cause an actual Fire Alarm.
Operation
Situation
Sounder
LED
Wireless Signal
to Panel
Recovery
Actual smoke
Temporal 3
(Loud)
RED
(pulsing)
Wireless Fire
Alarm Signal sent
to panel
When smoke is no
longer present.
TEST button will
silence sensor for 10
minutes.
Press & hold
Test Button
Temporal 3
(Loud)
RED
(pulsing)
Sensor Open
signal to panel
Sensor: Release
button.
Panel: Restore when
TEST button is
released
Removing
Sensor from
Mount
Temporal 3
(Loud)
Yellow
(steady)
Tamper/Trouble
signal to be sent
to panel.
Restore by
remounting.
Low Battery
1 Chirp every
43 seconds
Yellow
(pulsing)
Low battery
Hourly Check
Supervisories,
every hour
Maintenance
Needed
Temporal 3
(Loud)
Yellow
(Pulsing)
Supervisories Not
Sent
Replace Unit
Available for…
GE
Honeywell
DSC
2GIG
RE112_GE-Compat_Smoke_Instructions
Page 2 of 3
29-Oct-14
24-Hour Tech Support Line: (715)808-0164
www.ResolutionProducts.com
Specifications
Approval:
UL217 Self-Contained Fire Alarm Device
Smoke Sensitivity:
1.31 – 2.28 %/ft (UL 217)
0.11 – 0.165 dB/m (EN54-7)
Smoke Sensing Technology:
Photoelectric
521)
Alarm Sound:
Temporal Three
Replacement Battery:
Panasonic CR123A
Temperature Range:
32 to 120 F (Long Term)
Humidity:
10 – 85% Relative Humidity
Housing dimensions:
4.7 inch diameter, 2.1 inch high
Design & Manufacture:
Resolution Products, Inc.
Specifications subject to change without notice.
Pictures
TEST Button
LED
Battery
+
Smoke Sensing
Element
Mounting
Tabs
Tamper
Heat Sensor