background image

RE112_GE-Compat_Smoke_Instructions 

Page 1 of 3 

29-Oct-14 

24-Hour Tech Support Line: (715)808-0164 

www.ResolutionProducts.com

 

 

 
 
 

 

 
RE112 GE-Compatible Smoke & Heat Alarm 

Features 

 

 

UL217 Self-Contained Fire Alarm Device 

 

Senses and alarms to Smoke per UL217 

 

Heat alarm at 144 degrees. 

 

Sleek design. 

 

Cover tamper. 

 

Strong, reliable RF signal. 

 

3-5 year battery life on Panasonic CR123A battery. 

 

Low Battery indication. 

 

Key Instructions

 

1.

 

Attach the mounting plate 
Locate on ceiling, as close to center as possible, away from corners.   
Some local codes may allow wall mounting. 
Mounting plate removes counter-clockwise 

2.

 

Insert battery with MINUS towards the RED lever.  Close battery door. 

3.

 

Enroll sensor in panel: 

 

a)

 

Place panel in Learn Sensor mode 

b)

 

Press & release the black tamper switch 
Sounder will continue beeping 3 times, until sensor is mounted. 

c)

 

Recommended GE Group # (26) 

4.

 

Testing:    

 

a)  Place panel in Sensor Test mode 

 

b)  Press & hold TEST button until you hear the sounder beep.   
d)

 

Panel will indicate the sensor is open, but Fire Alarm will not sound. 

NOTE: Using Smoke-in-a-Can will cause an actual Fire Alarm. 
 

Operation 

 

Situation 

Sounder 

LED 

Wireless Signal 
to Panel 

Recovery

 

Actual smoke 

Temporal 3  
(Loud) 

RED 
(pulsing) 

Wireless Fire 
Alarm Signal sent 
to panel 

When smoke is no 
longer present.  
TEST button will 
silence sensor for 10 
minutes. 

Press & hold 
Test Button 

Temporal 3 
(Loud) 

RED 
(pulsing) 

Sensor Open 
signal to panel 

Sensor: Release 
button. 
Panel: Restore when 
TEST button is 
released 

Removing 
Sensor from 
Mount 

Temporal 3 
(Loud) 

Yellow 
(steady) 

Tamper/Trouble 
signal to be sent 
to panel. 

Restore by 
remounting. 

Low Battery 

1 Chirp every 
43 seconds 

Yellow 
(pulsing) 

Low battery 

 

Hourly Check 

 

 

Supervisories, 
every hour 

 

Maintenance  
Needed 

Temporal 3 
(Loud) 

Yellow  
(Pulsing) 

Supervisories Not 
Sent

 

Replace Unit

 

 

 

  

Available for…

 

GE 

 

Honeywell

DSC 

 

2GIG

 

RE112_GE-Compat_Smoke_Instructions 

Page 2 of 3 

29-Oct-14 

24-Hour Tech Support Line: (715)808-0164 

www.ResolutionProducts.com

 

 

Specifications   
 

Approval: 

 

 

UL217 Self-Contained Fire Alarm Device 

Smoke Sensitivity:   

1.31 – 2.28 %/ft (UL 217) 

 

0.11 – 0.165 dB/m (EN54-7) 

Smoke Sensing Technology: 

Photoelectric 

 521) 

Alarm Sound: 

Temporal Three 

Replacement Battery: 

Panasonic CR123A 

Temperature Range: 

32 to 120 F (Long Term) 

Humidity: 

 

 

10 – 85% Relative Humidity 

Housing dimensions: 

4.7 inch diameter, 2.1 inch high 

 
Design & Manufacture:  

Resolution Products, Inc. 

 
Specifications subject to change without notice. 
 

Pictures 

 

TEST Button 

LED

 

Battery

 

+

 

Smoke Sensing 

Element 

 

Mounting 

Tabs

 

Tamper 

 

Heat Sensor 

Reviews: