Heat quantity measurement
The heat quantity measurement can be carried out in 3 different ways (see below): 
with a fixed flow rate value, with a VFD Grundfos Direct Sensor™ or with a PWM 
feedback signal.

Heat quantity measurement with fixed flow rate value
The heat quantity balancing (estimation) uses the difference between the collector 
and the store base temperatures and the entered flow rate (at 100 % pump speed).

 

Î

Read the flow rate (l/min) and adjust it in the FMAX channel.

 

Î

Adjust the antifreeze type and concentration of the heat transfer fluid in the 
channels MEDT and MED%.

FMAX
Flow rate in l/min
Adjustment  range:  0.5 … 100.0
Factory setting: 6.0

Note:
The FMAX channel will be available only if the SEN channel has been set 
to OFF or if no VFD Grundfos Direct Sensor™ is activated.

Heat quantity measurement with a VFD Grundfos Direct Sensor
In order to use a VFD Grundfos Direct Sensor™ for heat quantity measurement, 
proceed as follows:

 

Î

Register the VFD Grundfos Direct Sensor™ in the GFD channel.

 

Î

Adjust the position of the VFD Grundfos Direct Sensor in the SEN channel.

 

Î

Adjust the antifreeze type and concentration of the heat transfer fluid in the 
channels MEDT and MED%.

Heat quantity measurement with a PWM feedback signal
In order to use a VFD Grundfos Direct Sensor™ for heat quantity measurement, 
proceed as follows:

 

Î

Register the PWM feedback signal of a bidirectional HE pump on the PFB 
channel.

 

Î

Adjust the antifreeze type and concentration of the heat transfer fluid in the 
channels MEDT and MED%.

The VFD Grundfos Direct Sensor™ can optionally be used for measuring the tem-
perature:

 

Î

Register the VFD Grundfos Direct Sensor™ in the GFD channel.

 

Î

Adjust the position of the VFD Grundfos Direct Sensor™ in the SEN channel.

Note
if a VFD Grundfos Direct Sensor™ is optionally activated, it will not be 
used for measuring the flow rate but for measuring the flow and return 
temperature respectively.

Note
If the PWM feedback signal sends an error message, heat quantity meas-
urement will not be carried out.

SEN
Digital flow rate sensor (only if GDF = 12, 40 or 40 F)
Selection: OFF, 1, 2
Factory setting: 2
Flow rate detection type:
OFF : PWM feedback signal or fixed flow rate value (flowmeter)

: PWM feedback signal or Grundfos Direct Sensor™ in the flow pipe

: PWM feedback signal or Grundfos Direct Sensor™ in the return pipe

Sensor allocation for heat quantity measurement:

1

2

OFF

SFL

SRET

SFL

SRET

SFL

SRET

GFD

S4

S1

GFD

S1

S2

Summary of Contents for DeltaSol AL EHE

Page 1: ...keep this manual safe DeltaSol AL EHE Solar controller for standard solar systems with electric backup heating Manual for the specialised craftsman Installation Operation Functions and options Troubl...

Page 2: ...ght from us and guarantee an environmentally sound disposal of the devices Safety advice Please pay attention to the following safety advice in order to avoid danger and damage to people and property...

Page 3: ...erview 4 2 Installation 5 2 1 Mounting 5 2 2 Electrical connection 6 2 3 Grundfos Direct SensorTM 7 2 4 PWM interface 7 2 5 Data communication Bus 7 2 6 Terminal allocation with cable link 8 2 7 Termi...

Page 4: ...nt relay Power supply 100 240V 50 60 Hz Supply connection type X attachment Standby 0 67 W Temperature controls class I Energy efficiency contribution 1 Mode of operation type 1 B Y action Rated impul...

Page 5: ...ease pay attention to separate routing of sensor cables and mains cables Unscrew the crosshead screw from the cover and remove the cover Mark the upper fastening point on the wall Drill and fasten the...

Page 6: ...rminals mains terminals VBus 1 2 S1 S2 S3 S4 3 4 5 6 T2A 100 240V 50 60 Hz VBus 9 10 11 12 13 14 DeltaSol AL E HE 1 1 A 100 240 V 14 3 A 100 240 V R1 R2 IP 20 Made in Germany 7 8 PWM PFB LED N N N 17...

Page 7: ...elay as well as to the PWM output of the controller Power is supplied to the HE pump by switching the corresponding relay on or off The terminal marked PFB is an interface for a bidirectional HE pump...

Page 8: ...y shutdown option OSEM Sensor S4 can optionally be connected For heat quantity measurement S1 and S2 S1 andVFD orVFD and S4 respectively can be used as flow and return sensors WARNING Electric shock U...

Page 9: ...4 can optionally be connected For heat quantity measurement S1 and S2 S1 andVFD orVFD and S4 respectively can be used as flow and return sensors WARNING Electric shock Upon opening the housing live pa...

Page 10: ...utton in order to scroll to the last display channel then press and hold down button for approx 3s If an adjustment channel is shown on the screen will be displayed on the right hand side next to the...

Page 11: ...e Antifreeze function activated Antifreeze function active Manual mode relay 1 ON Manual mode relay 2 ON Manual mode relay 1 2 OFF Sensor fault PWM feedback error message 3x Rapid heat up not possible...

Page 12: ...day mode Slide switch position left Backup heating off There will be no backup heating or thermal disinfection The upper heat exchanger in the System Monitoring Display will not be indicated S3 will n...

Page 13: ...n Fr ES It Factory setting dE 2 Temperature unit Adjust the desired unit UNIT Temperature unit Selection F C Factory setting C 3 Time Adjust the clock time First of all adjust the hours then the minut...

Page 14: ...peed Adjust the maximum speed for the corresponding pump nMX Maximum speed Adjustment range 10 30 100 Factory setting 100 Note The pump speed must be set to 100 when auxiliary relays or valves are con...

Page 15: ...iption Factory setting Page DT O x Switch on temperature difference R1 6 0 K 12 0 Ra 20 DT F x Switch off temperature difference R1 4 0 K 8 0 Ra 20 DT S x Set temperature difference R1 10 0 K 20 0 Ra...

Page 16: ...90 min 29 ODB x Drainback option OFF 29 tDTO x ODB switch on condition time period 60 s 30 tFLL x ODB filling time 5 0 min 30 tSTB x ODB stabilisation time 2 0 min 30 OTD s Thermal disinfection option...

Page 17: ...DB filling time active Indicates the time adjusted in tFLL running backwards Stabilisation STAB ODB stabilisation in progress Indicates the time adjusted in tSTB running backwards Indication of rapid...

Page 18: ...t Sensor Note S3 and S4 will only be indicated if the temperature sensors are connected to the corresponding terminals VFD will be indicated only if a Grundfos Direct Sensor has been connected and reg...

Page 19: ...e display returns to the display mode Indication of thermal disinfection CDIS Countdown of the Monitoring period Display range 0 30 0 24 dd hh If the thermal disinfection option OTD is activated and t...

Page 20: ...Adjustment range 1 0 20 0 K 2 0 40 0 Ra Factory setting 6 0 K 12 0 Ra The controller works as a standard differential controller If the temperature reach es or exceeds the switch on temperature diffe...

Page 21: ...e maximum pump speed of 100 is reached If the temperature difference decreases by the adjustable rise value pump speed will be decreased by one step Note The set temperature difference must be at leas...

Page 22: ...voltage Err4 The pump stops but is operable external cause installation hydraulics Err5 The pump stops but is not operable internal cause electronics pump is stuck Err6 PWM feedback signal connection...

Page 23: ...3 cooling functions collector cooling system cooling and store cooling are described in detail The following note is valid for all 3 cooling functions Note The cooling functions will not become activ...

Page 24: ...ling function OCC is deactivated Store cooling OSTC Store cooling option Adjustment range OFF ON Factory setting OFF OHOL Holiday cooling option Adjustment range OFF ON Factory setting OFF THOL Holida...

Page 25: ...TC or OCF is active the collector minimum limitation will be over ridden In this case the collector temperature may fall below CMN Antifreeze function OCF Antifreeze function option Adjustment range O...

Page 26: ...run at the adjusted minimum speed If the collector sensor is defective or the collector is blocked this function is suppressed or switched off TCEN Tube collector function ending time Adjustment range...

Page 27: ...centration of the heat transfer fluid in the channels MEDT and MED Heat quantity measurement with a PWM feedback signal In order to use a VFD Grundfos Direct Sensor for heat quantity measurement proce...

Page 28: ...switch on temperature BH O relay R2 is energised for backup heating If the thermostat switch off temperature BH F is exceeded the relay switches off The thermostat function is deactivated if the ther...

Page 29: ...mperature at sensor S3 exceeds the adjusted switch off temper ature BH F while rapid heat up is being activated rapid heat up will be blocked Drainback option Note A drainback system requires addition...

Page 30: ...2 0min The parameter tSTB is used for adjusting the time period during which the switch off condition will be ignored after the filling time has ended Thermal disinfection of the upper DHW zone OTD T...

Page 31: ...f the monitoring period ends for example at 12 00 o clock and the starting time has been set to 18 00 the reference relay will be energised with a delay of 6 hours at 18 00 instead of 12 00 o clock No...

Page 32: ...es in F and Ra are displayed without units If the indication is set to C the units are displayed with the values Reset RESE Reset function By means of the reset function all adjustments can be set bac...

Page 33: ...p is already active it will be deactivated If rapid heat up is active on the controller the LED of the RCTT will be perma nently red If rapid heat up is not possible because the temperature at sensor...

Page 34: ...6 100 212 1385 40 104 1155 105 221 1404 45 113 1175 110 230 1423 50 122 1194 115 239 1442 Resistance values of Pt1000 sensors Operating control LED flashes red The symbol is indicated on the display a...

Page 35: ...tarts for a short moment switches off switches on again etc Temperature difference at the controller too small Wrong position of collector sensors Plausibility control of the option tube collector spe...

Page 36: ...e connections insulated Insulate the connections Warm water outflow upwards Change connection and let the water flow sidewards or through a siphon downwards less store losses now o k a Does the DHW ci...

Page 37: ...essories Sensors Overvoltage protection device RCTT Remote control SD3 Smart Display GA3 Large Display AM1 Alarm module DL2 Datalogger DL3 Datalogger VBus USB VBus LAN interface adapters KM2 Communica...

Page 38: ...or router It enables easy access to the controller via the local network of the owner DL2 Datalogger For visualisation viaVBus net incl SD card and network cable mains adapter and VBus cable pre conne...

Page 39: ...quantity measurement 27 Holiday 12 24 L Language 32 M Manual mode 12 31 Minimum collector temperature 25 O Operating hours counter 20 P Pump control type 21 PWM feedback 22 PWM interface 7 PWM signal...

Page 40: ...r the completeness of the drawings and texts of this manual they only represent some examples They can only be used at your own risk No liability is assumed for incorrect incomplete or false informati...

Reviews: