resideo SmartValve SV9401 Installation Instructions Manual Download Page 14

SV9401/SV9402/SV9403, SV9501/SV9502/SV9503, SV9601/SV9602 SMARTVALVE™

69-1004—01

14

Fig. 14. SV9401/SV9402/SV9403, SV9501/SV9502/SV9503, SV9601/SV9602 SmartValve troubleshooting 

sequence.

INSTRUCTIONS TO THE 
HOMEOWNER

WARNING

Fire or Explosion Hazard. Can cause property 

damage, severe injury, or death.

Follow these warnings exactly:

1.

Do not light the pilot flame manually.

2.

Before lighting the pilot burner flame, smell around 

the appliance for gas. Be sure to smell next to the 

floor because LP gas is heavier than air.

WARNING

Fire or Explosion Hazard. Can cause property 

damage, severe injury, or death.

If you smell gas:

• Turn off the gas supply at the appliance service valve. 

On LP gas systems, turn off the gas supply at the gas 

tank.

• Do not light any appliances in the house.

• Do not touch electrical switches or use the phone.

• Leave the building and use a neighbor’s phone to call 

your gas supplier.

• If you cannot reach your gas supplier, call the fire 

department.

START

•  TURN OFF GAS SUPPLY
•  ASSURE SmartValve SWITCH IS IN ON POSITION
•  DISCONNECT SYSTEM CONTROL HARNESS
•  SET THERMOSTAT TO CALL FOR HEAT

CHECK FOR PROPER VOLTAGE AT CONTROL 
HARNESS (SEE INSET A). VOLTAGE SHOULD BE 
24V BETWEEN THERMOSTAT OR PRESSURE 
SWITCH AND 24V COMMON, AND 24V 
BETWEEN 24V COMMON AND 24V HOT.

CHECK:
•   LINE VOLTAGE POWER
•   LOW VOLTAGE TRANSFORMER
•   LIMIT CONTROLLER
•   THERMOSTAT
•   WIRING
•   AIR PROVING SWITCH ON COMBUSTION AIR 
    BLOWER SYSTEM
•   VENT DAMPER (IF USED) IS OPEN AND END 
    SWITCH MAKES

PLUG HARNESS INTO SmartValve  CONTROL. 
WAIT FOR INTERNAL CHECK DELAY 
(SV9X01, SV9X03) OR PREPURGE (SV9X02)

IGNITER WARMS UP AND GLOWS RED

•  TURN ON GAS SUPPLY
•  PILOT BURNER LIGHTS

MAIN VALVE OPENS AND MAIN BURNER LIGHTS

SYSTEM IS OKAY

WITH PILOT BURNER CABLE CONNECTED, MEASURE 
VOLTAGE AT SmartValve HSI ELEMENT 
OUTPUT (SEE INSET B) 24V NOMINAL.

YES

REPLACE IGNITER/FLAME ROD ASSEMBLY

REPLACE IGNITER/FLAME ROD ASSEMBLY

CHECK THAT PILOT GAS IS FLOWING.  WAIT TO 
ASSURE PILOT GAS TUBING IS PURGED.  RECYCLE 
CALL FOR HEAT IF NECESSARY.

MEASURE VOLTAGE BETWEEN 24V HOT AND 24V 
COMMON LEADS TO SmartValve CONTROL.  MUST 
MEASURE AT LEAST 19.5 VAC WITH IGNITER 
POWERED.  SEE INSET A TO IDENTIFY PROPER LEAD.  
THIS CHECK MUST BE DONE WITH THE SmartValve 
CONTROL CONNECTED AND IGNITER POWERED.

•   CHECK THAT PILOT FLAME MAKES GOOD 
    CONTACT WITH PILOT BURNER FLAME ROD.
•   ASSURE PILOT MOUNTING BRACKETS AND 
    PILOT BURNER ARE NOT BENT OR DAMAGED.
•   CHECK GAS SUPPLY PRESSURE.
•   CHECK PILOT BURNER ORIFICES FOR  
    CONTAMINATION OR DAMAGE  
•   CHECK FOR GOOD ELECTRICAL CONNECTION 
    THROUGH THE PILOT TUBING.
•   IF ALL OF THE ABOVE ARE GOOD, REPLACE 
    IGNITER/FLAME ROD ASSEMBLY

CYCLE THERMOSTAT OFF AND BACK ON

MAIN BURNER LIGHTS

REPLACE SmartValve CONTROL

REPLACE SmartValve CONTROL

REPLACE SmartValve CONTROL

CHECK TRANSFORMER AND LINE 
VOLT SUPPLY

NO

NO

NO

NO

NO

NO

NO

NO

NOTE: BEFORE TROUBLESHOOTING, 
BECOME FAMILIAR WITH THE STARTUP 
AND CHECKOUT PROCEDURE. ALSO 
CHECK PILOT BURNER ELEMENT FOR 
RESISTANCE LESS THAN 10 OHMS WITH 
ELEMENT AT ROOM TEMPERATURE.

24 VOLT
THERMOSTAT
OR PRESSURE
SWITCH

24 VOLT
COMMON

EFT 
OUTPUT

24 VOLT 
HOT

INSET A

INSET B

HSI
TERMINALS

YES

YES

YES

YES

YES

YES

M17217A

END VIEW 
OF CONTROL 
HARNESS
CONNECTOR

CHECK FOR DAMAGED OR MISSING 
TERMINALS  IN CONNECTOR

SV9X01/SV9X02/SV9X03 SmartValve™ TROUBLESHOOTING SEQUENCE

1

1

2

2

2

1

2

IGNITER WILL CYCLE OFF AND BACK ON ONCE DURING THE
90 SECOND IGNITION TRIAL. ALL VOLTAGE MEASUREMENTS
MUST BE TAKEN WHILE THE IGNITER IS POWERED.  

WHEN MEASURING VOLTAGE AT CONNECTIONS, USE 
CARE TO ASSURE TERMINALS ARE NOT DAMAGED.

Summary of Contents for SmartValve SV9401

Page 1: ... the appliance manufacturer See Table 2 for gas capacity and thread sizes SPECIFICATIONS WARNING Fire or Explosion Hazard Can cause property damage severe injury or death The SV9401 SV9402 SV9403 SV9501 SV9502 SV9503 SV9601 SV9602 provide direct replacement only Use the Y8610 to convert standing pilot systems to electronic ignition systems Ignition Sequences See Table 1 for available ignition sequ...

Page 2: ...esponse Time 1 6 seconds maximum at 3 mA IMPORTANT All timings increase by 20 percent with 50 Hz input Gas Conversion Kits See Table 5 for gas conversion kit information NOTE See appliance manufacturer specifications and instructions and information in these installa tion instructions before attempting to convert an appliance Pipe Adapters Angle and straight flange adapters available for 3 8 1 2 a...

Page 3: ...leaned with water or steam protect cover the control and wiring from water or steam flow Mount the control high enough above the bottom of the cabinet so it does not get wet during normal cleaning procedures High Humidity or Dripping Water Dripping water can cause the control to fail Never install an appliance where water can drip on the control In addition high ambient humidity can cause the cont...

Page 4: ...ide Converting Ignition System Control from Natural Gas to LP Gas Application or LP Gas to Natural Gas Application WARNING Fire or Explosion Hazard Can cause product damage severe injury or death Follow these warnings exactly 1 Do NOT attempt to convert step opening models SV9401P SV9402P SV9403P SV9501P SV9502P SV9503P or SV9601P SV9602P 2 Always change the main and pilot burner orifices when con...

Page 5: ...ibule on the gas manifold IMPORTANT Make sure the mounting location protects the control from dripping water and excessive humidity IMPORTANT Make sure the mounting location maximum and minimum ambient temperature are both within the specified acceptable range Install Piping on Control All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 ...

Page 6: ...or deform the tubing Do not bend the tubing at the ignition system control after the com pression nut is tightened because this can result in gas leakage at the connection 2 Square off and remove burrs from the end of the tubing 3 Unscrew the brass compression fitting from the pilot outlet as shown in Fig 6 4 Slip the fitting over the tubing and slide out of the way as shown in Fig 7 5 Push the tu...

Page 7: ...er controls as required 2 Connect control circuit to the ignition system con trol using the keyed plug connector See Fig 8 through 11 Fig 7 Always use new compression fitting Fig 8 SV9401 SV9402 SV9403 SV9501 SV9502 SV9503 SV9601 SV9602 basic wiring diagram CONTROL IGNITER OFF ON OUTLET PRESSURE TAP PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW INLET PRESSURE TAP INLET IGNITION SYSTEM CONTROL SWIT...

Page 8: ...MOTOR LEADS C X XFMR SEC X EAC N HUM N CIR BLWR CONT COOL HEAT 24 VOLT COMMON 24 VOLT HOT EFT OUTPUT 24 VOLT THERMOSTAT OR PRESSURE SWITCH INDUCER MOTOR HUMIDIFIER DENOTES LINE VOLTAGE WIRING DENOTES LOW VOLTAGE WIRING 2 1 ST9120 NEUTRAL NOTE 3 1 2 CONNECT ONLY IF CONTINUOUS SPEED IS AVAILABLE AND USED CONNECT ONLY IF CONTINUOUS SPEED IS NOT USED CONNECT IF EAC AND HUM TERMINALS ARE AVAILABLE AND ...

Page 9: ...ontrol with rich soap and water solution Bubbles indicate a gas leak 2 If a leak is detected tighten the pipe connections 3 Stand clear of the main burner while lighting to prevent injury caused from hidden leaks that could cause flashback in the appliance vestibule Light the main burner 4 With the main burner in operation paint the pipe joints including adapters and the control inlet and outlet w...

Page 10: ... with main burner operating NOTE Check the inlet pressure before adjusting the pressure regulator Standard M and Slow Opening H Pressure Regulator Models 1 Carefully check the main burner lightoff to make sure the burner lights smoothly and all the ports remain lit 2 Check the full rate manifold pressure listed on the appliance nameplate The ignition system control full rate outlet pressure should...

Page 11: ...anging between LP and natural gas Table 8 Pressure Regulator Specification Pressures in wc kPa MAINTENANCE WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Do not attempt to take the control apart or clean it Improper cleaning or reassembly can cause gas leakage Regular preventive maintenance is important in applications such as in the commercial cooking and agricu...

Page 12: ...sure the appliance is powered with the gas supply turned on Make sure the ignition system control switch is in the ON position TROUBLESHOOTING If Main Burner Will Not Come On With Call for Heat 1 Make sure the appliance has power and the gas supply is turned on 2 Make sure the ignition system control switch is in the ON position 3 Adjust the thermostat several degrees above room temperature 4 If t...

Page 13: ...WERED PILOT LIGHTS AND FLAME IS SENSED DURING TRIAL FOR IGNITION IGNITER OFF MAIN VALVE OPENS FLAME SIGNAL LOST ELECTRONIC FAN TIMER EFT OUTPUT ENERGIZES THERMOSTAT CALL FOR HEAT ENDS MAIN AND PILOT VALVES CLOSE EFT OUTPUT DE ENERGIZES MAIN AND PILOT VALVES CLOSE EFT OUTPUT DE ENERGIZES FIVE MINUTE RETRY DELAY WAIT FOR FLAME SIGNAL TO DISAPPEAR PILOT VALVE IGNITER REMAIN OFF PILOT VALVE CLOSES IGN...

Page 14: ...ND MAIN BURNER LIGHTS SYSTEM IS OKAY WITH PILOT BURNER CABLE CONNECTED MEASURE VOLTAGE AT SmartValve HSI ELEMENT OUTPUT SEE INSET B 24V NOMINAL YES REPLACE IGNITER FLAME ROD ASSEMBLY REPLACE IGNITER FLAME ROD ASSEMBLY CHECK THAT PILOT GAS IS FLOWING WAIT TO ASSURE PILOT GAS TUBING IS PURGED RECYCLE CALL FOR HEAT IF NECESSARY MEASURE VOLTAGE BETWEEN 24V HOT AND 24V COMMON LEADS TO SmartValve CONTRO...

Page 15: ...eset the safety control 2 Disconnect all electric power to the appliance 3 Remove the ignition system control access panel 4 Move the ignition system control switch to the OFF position 5 Wait five minutes to clear out any unburned gas If you then smell gas STOP Follow the Warnings above If you do not smell gas continue with the next step 6 Move the ignition system control switch to the ON position...

Page 16: ...Resideo Technologies Inc All rights reserved This product is manufactured by Resideo Technologies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Douglas Drive North Golden Valley MN 55422 1 800 468 1502 69 1004 01 M S Rev 04 20 Printed in United States ...

Reviews: