background image

SV9401/SV9402/SV9403, SV9501/SV9502/SV9503, SV9601/SV9602 SMARTVALVE™

69-1004—01

10

repair as necessary. If the pilot flame is hard and noisy, 

the inlet gas pressure may be too high. The ignition 

system control has a pilot adjustment mechanism to 

reduce the pilot flow, if necessary. Use the following 

procedure:

1.

Remove pilot adjustment cover screw. See Fig. 4. 

• Pilot adjustment is shipped at full flow rate.

2.

Turn the inner adjustment screw clockwise if the 

inlet pressure is too high.

• If the adjustment screw is used to reduce pilot 

flow rate, the pilot flame can become too small 

for reliable system operation if the system inlet 

pressure drops significantly.

3.

Replace the cover screw after the adjustment to 

prevent gas leakage.

Fig. 12. Proper flame adjustment.

Check and Adjust Gas Input and 
Burner Ignition

IMPORTANT

1. Do not exceed input rating stamped on the 

appliance nameplate.

2. Do not exceed manufacturer’s recommended 

burner orifice.

3. Make certain primary air supply to main burner 

is adjusted properly for complete combustion.

4. Follow appliance manufacturer instructions.

Checking Gas Input by Clocking Gas 
Meter

IMPORTANT

1. Make sure there is no gas flow through the 

meter except to the appliance being checked. 

Other appliances must remain off with their pilot 

lights extinguished. Otherwise, subtract that 

usage from the meter reading.

2. Convert the flow rate to Btuh as described in 

Gas Controls Handbook, form 70-2602.

3. Compare actual Btuh to the input rate on the 

appliance nameplate.

Checking Gas Input with Manometer

IMPORTANT

1. Make sure the ignition system control is in the 

OFF position before removing outlet pressure 

tap plug to connect manometer (pressure 

gauge).

2. Shut off gas supply at the manual valve in the 

gas piping to the appliance or, for LP, at the tank.

3. Move the ignition system control switch to the 

OFF position when removing the gauge and 

replacing the plug.

4. Remove inlet pressure tap plug.

5. Shut off gas supply.

6. Disconnect manometer and replace plug.

7. Repeat Gas Leak Test at plug with main burner 

operating.

NOTE:

Check the inlet pressure before adjusting the 

pressure regulator.

Standard (M) and Slow-Opening (H) 
Pressure Regulator Models

1.

Carefully check the main burner lightoff to make 

sure the burner lights smoothly and all the ports 

remain lit.

2.

Check the full rate manifold pressure listed on the 

appliance nameplate. The ignition system control 

full rate outlet pressure should match this rating.

3.

With the main burner operating, check the ignition 

system control flow using the meter clocking 

method or check pressure using a manometer con-

nected to the output pressure tap on the ignition 

system control.

4.

Adjust the pressure regulator (if necessary) to 

match the appliance rating. See Table 8 for factory 

set nominal outlet pressure and adjustment range.

a.  Remove the pressure regulator adjustment cap 

screw.

b. Using a screwdriver, turn the inner adjustment 

screw clockwise to increase or counterclock-

wise to decrease the gas pressure to the 

burner.

c. Replace the cap screw and tighten firmly to 

prevent gas leakage.

5.

If the desired outlet pressure or flow rate cannot be 

achieved by adjusting the ignition system control, 

check the ignition system control inlet pressure 

using a manometer at the inlet pressure tap of the 

ignition system control. If the inlet pressure is in 

the nominal range (Table 8), replace the ignition 

system control. Otherwise, take the necessary 

steps to provide proper gas pressure to the control.

NOTE:

If the burner firing rate is above 85,000 Btuh on 

SV9401/SV9402/SV9403 or 150,000 Btuh for 

SV9501/SV9502/SV9503 models (see Table 2 

for SV9601/SV9602 capacities), it may not be 

possible to deliver the desired outlet pressure. 

This is an application issue, not a control failure. 

Take whatever steps are required to correct the 

situation.

Step-Opening (P) Pressure 
Regulator Models

Step-opening models require you to check and adjust the 

full-rate pressure first and then check the step pressure. 

The step pressure is not field-adjustable.

PROPER FLAME 

ADJUSTMENT

HOT SURFACE

IGNITER 

FLAME ROD

M3350C

GROUND

ELECTRODE

3/8 TO 1/2 IN.

(10 TO 13 MM)

NOTE:  GROUND ELECTRODE MUST NOT TOUCH FLAME

 

ROD (.050 IN. MINIMUM CLEARANCE). BEND GROUND

 

ELECTRODE IF NECESSARY. DO NOT BEND FLAME ROD.

Summary of Contents for SmartValve SV9401

Page 1: ... the appliance manufacturer See Table 2 for gas capacity and thread sizes SPECIFICATIONS WARNING Fire or Explosion Hazard Can cause property damage severe injury or death The SV9401 SV9402 SV9403 SV9501 SV9502 SV9503 SV9601 SV9602 provide direct replacement only Use the Y8610 to convert standing pilot systems to electronic ignition systems Ignition Sequences See Table 1 for available ignition sequ...

Page 2: ...esponse Time 1 6 seconds maximum at 3 mA IMPORTANT All timings increase by 20 percent with 50 Hz input Gas Conversion Kits See Table 5 for gas conversion kit information NOTE See appliance manufacturer specifications and instructions and information in these installa tion instructions before attempting to convert an appliance Pipe Adapters Angle and straight flange adapters available for 3 8 1 2 a...

Page 3: ...leaned with water or steam protect cover the control and wiring from water or steam flow Mount the control high enough above the bottom of the cabinet so it does not get wet during normal cleaning procedures High Humidity or Dripping Water Dripping water can cause the control to fail Never install an appliance where water can drip on the control In addition high ambient humidity can cause the cont...

Page 4: ...ide Converting Ignition System Control from Natural Gas to LP Gas Application or LP Gas to Natural Gas Application WARNING Fire or Explosion Hazard Can cause product damage severe injury or death Follow these warnings exactly 1 Do NOT attempt to convert step opening models SV9401P SV9402P SV9403P SV9501P SV9502P SV9503P or SV9601P SV9602P 2 Always change the main and pilot burner orifices when con...

Page 5: ...ibule on the gas manifold IMPORTANT Make sure the mounting location protects the control from dripping water and excessive humidity IMPORTANT Make sure the mounting location maximum and minimum ambient temperature are both within the specified acceptable range Install Piping on Control All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 ...

Page 6: ...or deform the tubing Do not bend the tubing at the ignition system control after the com pression nut is tightened because this can result in gas leakage at the connection 2 Square off and remove burrs from the end of the tubing 3 Unscrew the brass compression fitting from the pilot outlet as shown in Fig 6 4 Slip the fitting over the tubing and slide out of the way as shown in Fig 7 5 Push the tu...

Page 7: ...er controls as required 2 Connect control circuit to the ignition system con trol using the keyed plug connector See Fig 8 through 11 Fig 7 Always use new compression fitting Fig 8 SV9401 SV9402 SV9403 SV9501 SV9502 SV9503 SV9601 SV9602 basic wiring diagram CONTROL IGNITER OFF ON OUTLET PRESSURE TAP PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW INLET PRESSURE TAP INLET IGNITION SYSTEM CONTROL SWIT...

Page 8: ...MOTOR LEADS C X XFMR SEC X EAC N HUM N CIR BLWR CONT COOL HEAT 24 VOLT COMMON 24 VOLT HOT EFT OUTPUT 24 VOLT THERMOSTAT OR PRESSURE SWITCH INDUCER MOTOR HUMIDIFIER DENOTES LINE VOLTAGE WIRING DENOTES LOW VOLTAGE WIRING 2 1 ST9120 NEUTRAL NOTE 3 1 2 CONNECT ONLY IF CONTINUOUS SPEED IS AVAILABLE AND USED CONNECT ONLY IF CONTINUOUS SPEED IS NOT USED CONNECT IF EAC AND HUM TERMINALS ARE AVAILABLE AND ...

Page 9: ...ontrol with rich soap and water solution Bubbles indicate a gas leak 2 If a leak is detected tighten the pipe connections 3 Stand clear of the main burner while lighting to prevent injury caused from hidden leaks that could cause flashback in the appliance vestibule Light the main burner 4 With the main burner in operation paint the pipe joints including adapters and the control inlet and outlet w...

Page 10: ... with main burner operating NOTE Check the inlet pressure before adjusting the pressure regulator Standard M and Slow Opening H Pressure Regulator Models 1 Carefully check the main burner lightoff to make sure the burner lights smoothly and all the ports remain lit 2 Check the full rate manifold pressure listed on the appliance nameplate The ignition system control full rate outlet pressure should...

Page 11: ...anging between LP and natural gas Table 8 Pressure Regulator Specification Pressures in wc kPa MAINTENANCE WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Do not attempt to take the control apart or clean it Improper cleaning or reassembly can cause gas leakage Regular preventive maintenance is important in applications such as in the commercial cooking and agricu...

Page 12: ...sure the appliance is powered with the gas supply turned on Make sure the ignition system control switch is in the ON position TROUBLESHOOTING If Main Burner Will Not Come On With Call for Heat 1 Make sure the appliance has power and the gas supply is turned on 2 Make sure the ignition system control switch is in the ON position 3 Adjust the thermostat several degrees above room temperature 4 If t...

Page 13: ...WERED PILOT LIGHTS AND FLAME IS SENSED DURING TRIAL FOR IGNITION IGNITER OFF MAIN VALVE OPENS FLAME SIGNAL LOST ELECTRONIC FAN TIMER EFT OUTPUT ENERGIZES THERMOSTAT CALL FOR HEAT ENDS MAIN AND PILOT VALVES CLOSE EFT OUTPUT DE ENERGIZES MAIN AND PILOT VALVES CLOSE EFT OUTPUT DE ENERGIZES FIVE MINUTE RETRY DELAY WAIT FOR FLAME SIGNAL TO DISAPPEAR PILOT VALVE IGNITER REMAIN OFF PILOT VALVE CLOSES IGN...

Page 14: ...ND MAIN BURNER LIGHTS SYSTEM IS OKAY WITH PILOT BURNER CABLE CONNECTED MEASURE VOLTAGE AT SmartValve HSI ELEMENT OUTPUT SEE INSET B 24V NOMINAL YES REPLACE IGNITER FLAME ROD ASSEMBLY REPLACE IGNITER FLAME ROD ASSEMBLY CHECK THAT PILOT GAS IS FLOWING WAIT TO ASSURE PILOT GAS TUBING IS PURGED RECYCLE CALL FOR HEAT IF NECESSARY MEASURE VOLTAGE BETWEEN 24V HOT AND 24V COMMON LEADS TO SmartValve CONTRO...

Page 15: ...eset the safety control 2 Disconnect all electric power to the appliance 3 Remove the ignition system control access panel 4 Move the ignition system control switch to the OFF position 5 Wait five minutes to clear out any unburned gas If you then smell gas STOP Follow the Warnings above If you do not smell gas continue with the next step 6 Move the ignition system control switch to the ON position...

Page 16: ...Resideo Technologies Inc All rights reserved This product is manufactured by Resideo Technologies Inc and its affiliates www resideo com Resideo Technologies Inc 1985 Douglas Drive North Golden Valley MN 55422 1 800 468 1502 69 1004 01 M S Rev 04 20 Printed in United States ...

Reviews: