6.2 Cleaning the magnet housing
1.
MHF49
2.
O-ring
3.
Filter mesh
4.
Removeable sheath
5.
Sealing ring
6.
Housing end cap
•
Make certain that the heating system is standing idle
properly, the pump must be switched off (see
manufacturer’s instructions for the heating system).
•
Close both isolation valves.
CAUTION!
Warning against hot water!
Hot water may cause burns.
When removing housing end cap hold abucket
below the filter to catch the exitingwater and debris.
•
Remove housing end cap [6].
•
Clean magnetic filter.
•
Screw the housing end cap [6] back on, applying a
torque of maximum 18 Nm ±10 %.
•
Make certain that the O-ring [2] is correctly positioned.
•
Unscrew the air vent cap from the top of the filter
housing. Open only the inlet isolation valve until water
exits the air vent hole.
•
Close the isolation valve.
•
Screw the air vent cap back on water tight.
•
Open both isolation valves.
7
Spare Parts
For the MHF49 there are no designated spare parts. In
normal operation no spare parts are needed. In case of
damage the whole MHF49 must be replaced.
8
Disposal
Both the MHF49 and the associated packaging consist mostly
of recyclable raw materials.
•
Dispose of packing and all recyclable materials
separately, properly and in an environmentally friendly
way.