Version: 1.0 | Date: April 2020 | Rev: 2020/04/02
LITHIUM IRON PHOSPHATE
SOLAR BATTERIES
QUICK START GUIDE
Page 1: ...Version 1 0 Date April 2020 Rev 2020 04 02 LITHIUM IRON PHOSPHATE SOLAR BATTERIES QUICK START GUIDE ...
Page 2: ...Ensure that you have the correct battery voltage for the charger inverter Do not use a 24V battery on a 48V system or vice versa With the charger inverter off measure the input impedance on the battery terminals to ensure there is no short circuit Connect the battery positive and negative terminals to the battery terminals of the charger inverter using the correct cable size and battery fuses brea...
Page 3: ... Measure the battery voltage with a voltmeter to determine the actual voltage If the red LED is permanently on the BMS has detected a health or safety event and disabled the battery Contact your supplier or Rentech Close the battery fuse breaker to connect the battery to the charger inverter Switch on the charger inverter while checking the battery current with a clamp meter to verify it is only t...
Page 4: ... 55 2 44 46 30 10080 0 50 24V 100 R 25 6 100 2560 2048 27 6 22 23 20 3360 0 50 24V 200 R 25 6 200 5120 4096 27 6 22 23 20 6720 0 50 Notes This applies to float and bulk charging Equalization charging should be disabled or also set to same charge voltage For batteries in parallel ensure the maximum charger inverter charge current is limited to the correct value or less of the number of batteries in...