background image

17

1.800.627.4499

EV-Series Premium

ERV

INSTALLATION

u

   Verify the unit has clean filters in place.

u

   Open the pressure port caps for the OA airstream and then insert the tubing into the openings 

about 1". 

u

   Take a differential pressure reading for the OA airstream and compare the pressure drop to 

the chart in Section 5.2.1 to obtain the CFM. Adjust the fan speed potentiometer (see Figure 
4.6.1) to obtain the desired CFM. Enter the CFM information in the box in Section 5.2.2.

u

   Take a differential pressure reading on the RA airstream and compare the pressure drop 

to the table in Section 5.2.1 to find the CFM of the RA airstream. Adjust the RA fan speed 
potentiometer to obtain the desired balance. Enter the CFM information into the box in 
Section 5.2.2.

u

   Install a jumper on the low voltage terminal to force the unit into Boost (high speed) mode. 

See the wiring diagram in Section 4.7.

u

   Repeat the process for both airstreams to set both the CFM and balance. Enter the 

information in the boxes in Section 5.1.

u

   After adjusting the potentiometers, take additional readings as needed to verify that fan 

speed settings are correct. See Figure 4.6.1.

FIGURE 4.6.0 PRESSURE PORT LOCATIONS

FIGURE 4.6.1 FAN SPEED CONTROL POTENTIOMETERS

www.renewaire.com     (800) 627- 4499 

[email protected]

www.renewaire.com     (800) 627- 4499 

[email protected]

POTENTIOMETERS ARE VISIBLE 

AND ACCESSIBLE THROUGH THE 

OPENING IN THE UNIT DOOR

NOTE: Adjust low 
speed fan set-
tings by using the 

potentiometers marked 
“L”. Adjust high speed 
fan settings by using the 
potentiometers marked 
with “H.”

www.renewaire.com     (800) 627- 4499 

[email protected]

USE THESE TWO PRESSURE PORTS TO 

CHECK PRESSURE DROP FOR THE RA 

AIRSTREAM

USE THESE TWO PRESSURE PORTS TO 

CHECK PRESSURE DROP FOR THE OA 

AIRSTREAM

Balancing an airflow is done by setting the Outdoor Air fan speed and then adjusting the Return 
Air fan speed to eject the same or somewhat less air to the outdoors.
Equipment required for testing airflows:

u

   A magnehelic gauge (or manometer) or other device capable of measuring 0–1.0 inches water 

gauge of differential pressure.

u

   2 pieces of natural rubber latex tubing, 1/8" I.D., 1/16" wall thickness works best.

Manometers are relatively inexpensive devices that are readily available from online retailers; 
accuracy within the range of 0–1.0 in. w.g. is the critical measure. Water manometers generally 
have graduations of 0.1" that are difficult to accurately determine. For all manometers, there 
are two plastic tubes that connect at the manometer and then the other ends go to pressure 
ports on the EV Premium. 
Individual differential static pressures (DP) are measured ACROSS the core, using the installed 
pressure ports located on the removable door.

Summary of Contents for EV Premium ERV Series

Page 1: ...Model EV Premium L shown EV Premium M EV Premium L EV SERIES Premium ERV Installation Operation and Maintenance Manual...

Page 2: ...work practices Always wear OSHA approved Personal Protective Equipment PPE CAUTION RISK OF CONTACT WITH HIGH SPEED MOVING PARTS This appliance has two high speed fans that can cause injury or be damag...

Page 3: ...ded from the Model Number UNIT INFORMATION EV Premium M EV Premium L NOTE This page is to be completed by the installing contractor The completed document is to be turned over to the owner after start...

Page 4: ...ock FM Push button point of use controls PBL PTL req d MERV 13 filter OA airstream shipped loose Electric duct heater RH series 1 4 kW designed for indoor ductwork installation only Energy Recovery Ve...

Page 5: ...RA FA 34 Line Cord Pressure Ports 4 Typ 23 3 4 Overall 12 5 8 Case 22 1 4 Minimum Service Area Door can be Removed from Hinges 22 1 4 Minimum Service Area Door Swing 8 Nominal Typ 6 Nominal Typ 7 8 T...

Page 6: ...utton point of use controls PBL PTL req d MERV 13 filter OA airstream shipped loose Electric duct heater RH series 1 4 kW designed for indoor ductwork installation only Energy Recovery Ventilator EC M...

Page 7: ...RA FA 34 Line Cord Pressure Ports 4 Typ 23 3 4 Overall 23 5 8 Case 22 1 4 Minimum Service Area Door can be Removed from Hinges 22 1 4 Minimum Service Area Door Swing 8 Nominal Typ 6 Nominal Typ 7 8 T...

Page 8: ...ETTINGS 16 4 6 BALANCING AIRFLOWS 16 4 7 WIRING SCHEMATICS 18 4 8 LOW VOLTAGE WIRING DIAGRAMS 19 4 8 1 Low Speed High Speed Modes Continuous 19 4 8 2 Low Speed Continuous High Speed SWITCHED 19 5 0 OP...

Page 9: ...r 13 Figure 2 4 4 Furnace Return Air back into Supply Air 13 Figure 2 6 0 EV Premium Filter Locations 14 Figure 2 7 0 Controls Terminal Strip 14 Figure 3 1 0 Mounting the ERV to a Stud Wall 15 Figure...

Page 10: ...des the best energy recovery Airflow can be adjusted using the motor potentiometers and the values read via the door pressure taps The hinged door has an opening for viewing and access to the potentio...

Page 11: ...r Outdoor Air Supply Air and the other fan is for the exhaust airstream Return Air Exhaust Air The speed of each fan is controlled independently by a 0 10 VDC signal from the controller The controller...

Page 12: ...resh conditioned air Supply Air from the EV Premium to a desired location in the residence The Supply Air duct may end in a floor or wall grate with an area of at least 28 square inches Alternatively...

Page 13: ...introduce FA at low velocity and where good mixing will oc cur to minimize discomfort from drafts www renewaire com 800 627 4499 support renewaire com NOTE ERV blower may be operated separate from fu...

Page 14: ...can be installed by one person www renewaire com 800 627 4499 support renewaire com 24 VAC COMMON HIGH SPEED BOOST MODE 120 VAC LINE CORD 2 6 FILTERS Each EV Premium is equipped at the factory with me...

Page 15: ...it for the simplest duct layout and connections May be installed in any position providing sufficient clearance as shown in the front of this manual Preferred position is horizontal so that the hinged...

Page 16: ...oned behind one or more ribs in the duct Observe Industry Best Practices when installing and supporting the ducts All low voltage connections are made on the exterior of the unit on the low voltage te...

Page 17: ...7 4499 support renewaire com www renewaire com 800 627 4499 support renewaire com POTENTIOMETERS ARE VISIBLE AND ACCESSIBLE THROUGH THE OPENING IN THE UNIT DOOR NOTE Adjust low speed fan set tings by...

Page 18: ...Power 115 VAC 1 Phase M SF Motor M EF Motor SF_ECM_LOW SF_ECM_HIGH Line Cord 120VAC 120COM 24VAC HIGH COM EF_ECM_HIGH EF_ECM_LOW Control Board BK RD YL BR BU GN YL BK RD YL BR BU GN YL WHT RD BK RD B...

Page 19: ...e terminal strip This wiring configuration will vary with each control sensor 5 0 OPERATION 5 1 MANOMETER READINGS AT COMMISSIONING Return Air Pressure Port In w g Exhaust Air Pressure Port In w g Out...

Page 20: ...g EXAMPLE 1 In w g of pressure drop across the core corresponds to 235 CFM of airflow So 1 In w g of pressure drop across the core corresponds to 235 CFM 0 5 In w g corresponds to 117 5 CFM and so on...

Page 21: ...libration is also required 6 3 DOOR REMOVAL The hinged door is held in place by two separable hinges on one edge and two security latches on the other edge The separable hinges have a spring loaded de...

Page 22: ...the house It may be necessary to hold a thin strip of tissue paper in front of a vent to realize whether or not there is airflow u Check for airflow in both low speed and high speed settings It will...

Page 23: ...r to an internal failure by bypassing the controlling device u Remove all wiring from the terminal strip as shown in Section 4 8 of this manual Mark the wires so they can be reconnected in their prope...

Page 24: ...bility derived from innovative design practices expert workmanship and Quick Response Manufacturing QRM As the pioneer of static plate core technology in North America RenewAire is the largest ERV pro...

Reviews: