Flue gas system
Requirements and regulations
Materials
Requirements and regulations
Regulations for the construction of flue
gas systems are very different for each
country. It should be ensured that all
national regulations with regard to flue
gas systems are respected. The most
important national norms can be found
in the chapter „Norms“.
A separate condensate drain for the
chimney is not necessary, as the
condensate can enter the drain via the
syphon connection of the boiler.
Materials
Exclusively materials, which are heat
resistant and resistant to flue gases and
aggressive condensate, may be used.
The R3456 EVO has an integrated high
limit thermostat function for the flue
gases. When the max flue gas
temperature is exceeded, the burner is
switched off. With this function, an
additional (external) safety device is not
necessary.
Plastic
PP
Stainless
steel
Temperature
class
T120
T250
Pressure
class
P1
-
Corrosion
class
W1
W1
The installer is responsible to apply the
correct diameter, length and type of flue
gas system. If any questions arise during
the calculation contact your local
manufacturer office for more information.
You have to take in consideration the
following material requirements:
Pressure
class
Temperature
class
Condensate
resistant
Corrosion
class
Fire
resistant
Flue resistance <200Pa
P1
Min:T120
W
V1,V2 or Vm
E or higher
200Pa<Flue resistance<5000Pa
H1
Min:T120
W
V1,V2 or Vm
E or higher
Pay attention to the following
recommendations when
dimensioning a flue gas system:
-
Only approved flue gas material
may be used.
-
The flue gas system must be
properly calculated to ensure a
safe functioning of the system.
-
Flue gas system components
should be removable for
maintenance purposes.
-
Horizontal flue gas ways must be
mounted under an angle of 3º
minimum.
23
Summary of Contents for R3456 EVO
Page 1: ...Planner Documentation R3456 EVO 06 2020...
Page 2: ......
Page 19: ...Extent of delivery Component Dimensions R3400 3500 3600 EVO 18 R3401...
Page 20: ...Extent of delivery Component Dimensions R3400 3500 3600 EVO 19 EVO...
Page 46: ...Accessories Standard pumps performance curves 45 Standard pumps performance curves...
Page 47: ...Accessories Standard pumps performance curves 46...
Page 50: ...Accessories Speed control pumps performance curves 49...
Page 51: ...Accessories Speed control pumps performance curves 50...
Page 52: ...Accessories Speed control pumps performance curves 51...
Page 70: ...66...
Page 71: ......
Page 72: ...Service www rendamax com...