Operation
Overview of display values and settings
Heating circuit I / II
Designation
Value range
Default
IV
MODE
----,
i
,
F
1,
F
2,
B
,
B
- - - -
T-ROOM DES 1*)
5°C - 40°C
20°C
T-ROOM DES 2
5°C - 40°C
20°C
T-ROOM DES 3
5°C - 40°C
20°C
ECONO TEMP*)
5°C - 40°C
10°C
REDUCED TEMP
5°C - 40°C
15°C
T-LIMIT DAY
----, (-5)°C - 40°C
19°C
T-LIMIT N
----, (-5)°C - 40°C
10°C
HEAT SLOPE
0,00 - 3,00
1,20
ADAPTION
00, 01 (OFF/ON)
00 = OFF
ROOMS-INFL
00 - 20
10
ADAP ROOM-T
(-5,0)K - (5,0)K
0,0K
OPTIMIZAT
00, 01, 02
00
M-OPT-TIME
0:00 - 3:00 [h]
2:00 [h]
ECONO OPTI
0:00 - 2:00 [h]
0:00 [h]
PC-ENABLE
0000 - 9999
0000
RETURN
Exit level using
Ä
~
Hinged cover OPEN
Î
search for
level to the right with
Ç
, open with
Ä
MODE
- - - - => The controller programming
switch applies in this case.
When setting an operating mode the
mode only applies to the assigned
heating circuit. When the "
i
= Stand-
by/OFF", and "
F
= Summer mode"
controller programming switch
operating modes are set, this has a
reducing effect on all heating circuits
and consumer circuits in the entire
system.
T-ROOM DES 1-3
Required room temperature setting
T-ROOM DES 1
=> used in first enable time,
T-ROOM DES 2
=> used in second enable time,
T-ROOM DES 3
=> used in third enable time of active
heating program for this heating circuit.
ECONO TEMP
Required room temperature setting
during night reduction
REDUCED TEMP
Required room temperature setting
during holidays
*) depending
on
function
selector
Heating
circuit
POOL-TEMP,
DHW-TEMP,
T-FLOW-DAY
or
T-FLOW-NIGHT (see page 24)
17
Summary of Contents for E8.1121