Operation
Overview of display values and settings
Start sensor test with
Ä
, use
Ç
to
select sensor => temperature is
displayed; Use
Ä
to stop sensor test
SENSOR TEST
Multifunction sensor according to
function set for relay
01 = Header pump
=> T-COLLECTOR = Collector
temperature (display only if sensor is
connected)
20 = Temperature-controlled circulation
pump
=> T-CIRCL = Temperature of circula-
tion pipe return
21 = Circulation pump via pulse
=> no temperature display (display
with ON/OFF)
Parameter CHARGE THROUGH at the
level Expert –Hot water is activated
(=01)
=> T-DHW LOWER = Temperature of
the hot water tank at the inlet area
22 = Integration of the heat generator
for solid fuel
=> SOLID FUEL-T = Temperature of
the heat generator for solid fuel,
=> T-BUFFER LOWER = Temperature
of the storage tank at the inlet area
23 = Solar integration
=> T-COLLECTOR = Temperature of
the solar collector,
=> T-BUFFER LOWER = Temperature
of the storage tank in the inlet area
24 = Return flow temperature increase
=> RETURN TEMP = Return tempera-
ture to HS
32 = Heating circuit direct
=> HEATCIRCUIT 3 (display ON/OFF)
T-MULTI SENS => Temperature
display without function selection
=> without sensor no display (- - - - )
Sensor test
=> Value group
(General -> Service level)
Select sensor using
Ç
=> value is displayed
OUTSIDE TEMP
Outside temperature
T-HS
Temperature of the heat generator
DHW-TEMP
Hot water temperature
FLOW TEMP
D
1
Flow temperature, heating circuit 1
T-ROOM
D
1
Room temperature heating circuit 1
(only with remote control)
T-FLOW
D
2
Flow temperature, heating circuit 2
T-ROOM
D
2
Room temperature heating circuit 2
(only with remote control)
T-RETURN
SOLID FUEL-T,
T-COLLECTOR
T-COLLECTOR
T-CIRCL
T-DHW LOWER
T-MULTI SENS1
Temperature of the multifunction
sensor => Display according to
function set for multifunction relay
(see left)
BUFFER-T-L
For solid fuel or solar integration
=> Sensor in storage tank
11