Instruction
Electric Actuators Ex-proof
RCEL005X/009X
- 1 -
www.rotork.com www.remotecontrol.se
ELECTRICAL SHOCK HAZARD.To avoid serious personal injury,
property damage, turn off ALL power to the actuator before remov-
ing the cover.
Before installation, verify the nameplate information information to
insure the correct model number and voltage of the actuator.
Be sure to completly review the actuator manual prior to operation.
Final limit switch adjustment MUST be done after mounting the ac-
tuator to the valve. Incorrect adjustment may cause actuator failure.
The actuator must be properly grounded. Use the grounding lugs
provided on the inside and outside of the actuator body.
To minimize the possible damage caused by condensation, be sure
to energize the heater.
Standard Specification
Enclosure
Weatherproof enclosure IP67
Nema 4 and 6
Ex d IIB T4
Ambient
temperature
-20 ºC to 55 ºC
Power Supply
110 / 220 / 230 Vac 1 Ph 50/60 Hz
24 Vac 1 Ph 50/60 Hz, 12/24 Vdc
Limit Switches
2 (Open/Close)
2 Dry (Open/Close)
Manual Operation
By 6 mm hex key
Space Heater
5 W (110 / 230 VAC, 12 / 24 VDC)
Lubrication
Grease Moly (EP type)
Surface Treatment
Anodizing
Travel Angle
90º ± 5º (extension: upto 270º)
Self Locking
Provided by means of worm
gearing
Entries
2 - M20
Materials
Steel, Aluminium alloy, Bronze
External Coating
Polyester (TGIC-free)
Optional Specification
005X
009X
PIU
Potentiometer Unit (1 K-Ohm)
X
X
CPT
Current Position Transmitter
Output DC 4~20 mA
X
X
PCU
Proportional Control Unit
Input: DC 4~20 mA, 2~10 V,
0~5 V,
0~10 V, 1~5 V
Output: DC 4~20 mA
X
X
LCU
Local Control Unit
X
X
Mod - Bus
X
X
Profi - Bus
X
X
Can - Bus
X
X
Explosion-proof products must be used under the designed temper-
ature range and environment appropriate for the product spec.
Explosion proof actuators and wiring must be properly sealed prior
to operation. Improper installation may cause a hazardous condition
and failure of the explosion proof enclosure. The manufacture is not
responsible for any losses or damages caused by incorrect installa-
tion.
1.
Certified cable entries must be used when installed. Use
separately certified cable entries, conduit entries or stopping
plugs so that the flameproof properties of the enclosure are
maintained.
2.
If conduit is used for cable entry, a seal fitting with setting com
-
pound must be installed as close as posible, within 450 mm to
the actuator.
Special conditions for safe use:
For information about the flameproof joints, please contact Rotork
Sweden AB.
Fasteners securing the top cover shall have the property class of
A2-50 at least.
CAUTION
CAUTION
Flameproof Enclosure Level and Enviroment of Actuator
Ex IIB T4 -20 ºC ~ 55 ºC
Performance
Model
Output
Torque
Operation Time (90º)
Motor *
Class (E)
Rated Current
Duty*
Cycle
Number
Of
Handle
Turns
Weight
kg
1 Phase (AC)
DC
Kg.m
Nm
60 Hz
50 Hz DC24V
W
24V
110V
220V
24V
S2 (min)
RCEL005X
5
50
14
17
10
6
1,8
0,35
0,23
1,8
15
6
5
RCEL009X
9
90
26
32
22
6
2,1
0,35
0,25
2,1
15
4,5
5
*Valid for 1-ph 110V AC and 220V AC