background image

- 1 -

Top Quality Valve Actuators 

Electric Actuators

RCEL 005 / 005L

Installation

1. Mounting on valve A).
2. Electric wiring (B).
3. Adjusting (C).
4. Manual operation (D).

NOTE: Only electric wiring, according to
instruction B, is required when the actuator
is delivered from Remote Control mounted
on a valve. It is adjusted and ready for
operation.

1.  Operate the valve manually to fully open
     or fully closed position before the actuator
     is mounted.
2.  Operate the actuator manually (see D) to
     fully open or fully closed position.
3.  Check that the actuator and valve stem
     are in correct position. Please note, valve
     and actuator must be in the same mode
     (fully open / fully closed) prior to the
     assembly.
4.  Mount the actuator on the valve and
     check that the actuator and valve stems
     are centered and aligned. If a mounting
     bracket is used, the fi t must be checked
     so that no distortion or play exists.
5.  Operate the valve manually with the aid of
     allen key (see D) and check that the valve
     moves with normal resistance.
6.  Check that all screws are correctly
     tightened.

1.  Loosen the screws on the cover and lift it off.
2.  Check the voltage marked on the actuator
     label.
3.  Connect according to the enclosed wiring
     diagram or, if the actuator is of standard
     design, according to the wiring diagram
     below. The wiring diagram is drawn in
     unaffected position (the valve in intermediate
     position).
4.  Test run the actuator from the intermediate
     position checking that the actuator turns in
     the correct direction.
5.  Test run the actuator and check that the limit
     switches work correctly.
6.  Check that the cable entries and possible
     blind plug are sealed.
7.  Mount the cover.

Wiring diagram No. ST 12000 A. Standard.

NOTE: Electric wiring must be carried out by
qualifi ed personnel only!

A. Mounting on Valve 

B. Electric Wiring

WARNING!

Remove power before the cover
is dismantled! The actuator must be handled 
with the utmost care when the cover is 
removed and the power is connected.

Instruction

Reviews: