Circulation type
(dependent on which probes are used)
Impulse circulation: (Only in conjunction with the REMKO impulse generator)
If briefly dispensing water triggers an impulse on the flow-operated safety device, this is registered by the
controller and the circulation pump is started up. This means that the circulation is also active when it is
required.
Temperature-guided circulation: (Only in conjunction with the REMKO S05 probe)
Temperature-guided circulation keeps the hot water temperature at the set temperature.
Select the circulation type.
Menu item
Parameter
Factory setting
Circulation type
Impulse circulation
As required
Temperature-guided circulation
Circulation set temperature - temperature-guided circulation
Desired set temperature for temperature-guided circulation.
This should be set at least 5 °C below the set temperature for the hot water storage tank, or even lower for
efficiency reasons.
Then set the desired temperature.
Menu item
Parameter
Factory setting
Temperature-guided circulation
25 °C - 65 °C
35 °C
Impulse-guided circulation - Running time of the circulation
Switch-on time of the circulation pump after a dispensing impulse.
If the circulation line is very short, a shorter running time may suffice. If the time is not sufficient to pump hot
water to a remote dispensing point, the running time must be extended.
Then select the desired temperature.
Menu item
Parameter
Factory setting
Impulse-guided circulation -
Running time of the circulation
1 min - 15 mins
5 min.
REMKO Smart-Control Touch
88