3. Set the standard outside temperature
1
Fig. 9: Set the standard outside temperature
The standard outside temperature [1] can be
changed for the user and the expert.
These parameters can be found in the level: "Set-
tings
"
heating/cooling
"
Building adaptation".
Here, it is possible to set the standard outside tem-
perature to the respective value for heating and
cooling mode.
The standard outside temperature is only changed
once here for each active heating cycle. After
changing this parameter, the value is automatically
accepted with all active heating cycles.
For optimal configuration of the heating curve
parameters, the heating load calculation and/or
energy consumption must be taken into account.
Differences between the installed parameters and
the design of the actual building can cause the
heat pump to run inefficiently.
Fixed-value-control heating cycle mode
Specify the set temperature for fixed value control.
The heating cycle is kept permanently at this tem-
perature in fixed value control. When doing so, a
tolerance of approx. 2 Kelvin is possible.
Operating the heating cycle with a fixed value is
not recommended, as it will cause the heat
pump to operate inefficiently.
The mixed heating cycles each require a supply
and return probe! These probes are included in the
scope of supply of the mixed REMKO heating
cycle groups.
Fig. 10: Setting the fixed value (set temperature)