n
Check whether the stopper in the condensate
drain is present and correctly installed. There is
a risk of uncontrolled condensate leakage after
commissioning.
1
Fig. 7: Condensate drain
1: Condensate drainage with stopper
n
Never operate the unit without the air inlet filter.
Otherwise, the fins of the heat exchanger can
become dirty and the unit loses performance.
1
Fig. 8: Air inlet filter
1: Recirculated air filter
n
Ensure that persons and sensitive objects,
such as plants, are not placed directly in the air
flow emerging from the unit.
In addition, with direct solar radiation close the
curtains and blinds and keep the windows and
doors closed during operation.
Conduct the warm exhaust air away
NOTICE!
The exhaust air hose should always be laid
rising in the direction of air flow and must not
be extended!
In cooling mode the unit creates warm moist
exhaust air, which must be conducted away from
the room to be cooled. For this reason it is neces-
sary to plug the exhaust air hose into the outlet
opening on the rear of the unit.
n
Ensure that the catches for the exhaust air
hose latch securely into the two openings of
the connection aperture. In order to be sure of
effective operation, do not lay the flexible
exhaust air hose with tight bends and do not
kink it and to prevent damage resulting to avoid
air carrying components!
Fig. 9: Latch the hose into place
n
The exhaust air of the unit contains a certain
amount of moisture. For this reason it is advis-
able to feed the exhaust air to the outdoor area
or to outdoors.
Exhaust air routing variants
You can route the exhaust air out of the building as
follows:
Via a flat nozzle
The flat nozzle supplied can be used in various dif-
ferent ways. It is possible to feed the flat nozzle
through an open window and fasten it by means of
Velcro and a window suction cup (Fig. 10). Like-
wise the flat nozzle can be hung in a tilted window
REMKO MKT
12