4
Assembly
4.1 Setting up the unit
For the best economic and safe use of the units,
the following notes must be followed in full:
n
The units must be set up in an upright and
level position, to ensure that the condensate
can drain freely
n
To ensure optimum air circulation, the units
should be set up in the centre of the room,
where possible
n
It must be ensured that the air can be sucked
in on the front of the unit and blown out of the
rear of the unit without obstruction
n
Observe a minimum clearance of 50 cm from
walls at all times
n
Units must never be set up in the immediate
vicinity of heaters or other sources of heat
n
The room being dried or dehumidified must be
closed to the surrounding atmosphere
n
Air circulation is improved if the unit is set up
approx. 1 m above the ground
n
Avoid having opened windows and doors etc.,
and avoid frequent entry to or exit from the
room as much as possible
n
If the units are to be used in dusty environ-
ments, appropriate care and maintenance
measures should be taken in accordance with
the relevant conditions
n
The output of the unit is entirely dependent on
the conditions inside the room, room tempera-
ture, relative humidity and observance of the
set-up instructions
n
The units may not be used in environments
containing a great deal of dust or chlorine, or in
places with atmospheres containing ammonia
0,5 m
0,5 m
Fig. 6: Setting up the unit
NOTES:
–
Keep windows and doors closed!
–
Keep at least 0.5 m away from walls.
–
Maintain adequate clearance from heaters
or other sources of heat.
4.2 Unit transport
For easy transportation, the units are equipped
with 2 large wheels and an ergonomic transporta-
tion handle and protective frame. This can also be
dismantled easily if required.
When transporting the units, observe the following:
1.
Before each change of location, switch off
the unit and remove the power plug from the
mains socket.
2.
Drain the condensate container.
3.
Only transport the units in an upright position
where possible.
4.
If the unit was transported on its side, you
must wait 1 hour with the unit in an upright
position before switching on.
NOTICE!
Beware of dripping condensate. After switching
off the units, the evaporator may continue to
defrost under the influence of the ambient tem-
perature.
WARNING!
The mains cable must never be used as a pull
cord or fixing device.
REMKO LTE
14