REMKO LTE 50 Assembly And Operating Instructions Manual Download Page 12

Energy must be supplied when liquid is converted

into a gas. This energy is designated as evapora-

tion heat. It does not cause any increase in tem-

perature, but is required to convert a liquid into a

gas. Conversely, energy is released when gas is

liquefied, this is designated as condensation heat.

The amount of energy from evaporation heat and

condensation heat is the same.

For water, this is: 2250 kJ/kg (4.18 kJ = 1kcal)

From this it is evident that the condensation of

water vapour causes a large quantity of energy to

be released. With drying operations, a heat cycle is

created, whereby heat is consumed for evapora-

tion and released for condensation.

Generally speaking, the time required for the

drying process is not only dependent on the

output of the unit, but is determined to a greater

extent by the speed at which the material or

building section loses its moisture.

3.2  Unit description

The units have been designed for universal and

straightforward air dehumidification.

Their compact dimensions allow the unit to be

transported and set up with ease.

The units operate in accordance with the conden-

sation principle and are equipped with a hermeti-

cally sealed refrigerant system, low-noise and low-

maintenance fan, operating hours and energy

counter as well as a connection cable with plug.

Fully-automatic electronic controller, a condensate

container with integrated overflow protection in

addition to connection ports for direct condensate

drainage help to ensure continuous fault-free oper-

ation.

The units conform to the fundamental health and

safety requirements of the appropriate EU stipula-

tions. The units are dependable and offer ease of

operation.

Locations at which units are used

The units are used in all locations, where dry air is

a must and where economic consequential

damage (such as that caused by mould) must be

prevented.

The units may be used for the drying and dehumid-

ification of areas such as:

n

New buildings, industrial buildings

n

Basements, storage rooms

n

Archives, laboratories

n

Weekend homes, caravans

n

Bathrooms, wash rooms and changing rooms

etc.

Operating sequence

Switching on the unit puts the electrical control into

operation. The green "COMP. ON" indicator light

on the control panel illuminates. Due to an auto-

matic pressure equalisation, the units start with a

time delay of around 10 seconds.

The fan extracts the moist room air through the

dust filter, evaporator and the condenser behind.

Heat is removed from the room air on the cold

evaporator. The air is then cooled to below dew

point. The water vapour contained in the room air

is then deposited as condensate or rime on the

evaporator fins.

If the temperature sensor here measures a pre-set

minimum, it activates a timer with a 30 minute

delay. If the evaporator temperature stops

increasing during this period, the cooling cycle

switches to hot gas defrosting after the timer cycle.

The fan remains out of operation during the

defrosting phase.

As soon as the rime (ice) has been defrosted and

the temperature at the probe has increased, the

unit switches back to normal dehumidification

mode.

If the room temperature is sufficiently high, the sur-

face of the fins will not be cold enough for rime for-

mation to occur, rendering defrosting unnecessary.

Therefore, the air dehumidifiers work economically.

The cooled and dehumidified air is re-heated by

the condenser (heat exchanger), and blown back

into the room through the outlet grille. The pro-

cessed, dry, heated air then re-mixes with the room

air.

Continuous circulation of the room air through the

unit gradually reduces the relative humidity (% RH)

in the room to the desired humidity level.

Depending on the room temperature and the

humidity, only 30-40% electrical energy is required,

in accordance with the output of the unit.

 

 

 

REMKO LTE

 

 

12

Summary of Contents for LTE 50

Page 1: ...Assembly and operating instructions Read the instructions prior to performing any task REMKO LTE 50 60 80 Dehumidifier 0153 2017 07 Edition 1 en_GB...

Page 2: ...g inal Read these operating instructions carefully before commis sioning using this device These instructions are an integral part of the system and must always be kept near or on the device Subject t...

Page 3: ...ng 6 1 12 Environmental protection and recycling 6 2 Technical data 7 2 1 Unit data 7 3 Design and function 9 3 1 Air dehumidification general note 9 3 2 Unit description 12 4 Assembly 14 4 1 Setting...

Page 4: ...ay be fatal or cause serious injury WARNING This combination of symbol and signal word warns of a potentially hazardous situation which if not avoided may be fatal or cause serious injury CAUTION This...

Page 5: ...location the conden sate container must be emptied n The units must be inspected by a service tech nician to ensure that they are safe to use and fully functional at least once yearly Visual inspecti...

Page 6: ...idered it is essential that the ordering party or its representative com plete and return the certificate of warranty to REMKO GmbH Co KG at the time when the units are purchased and commissioned The...

Page 7: ...frigerant 2 R410A Refrigerant quantity g 420 540 750 Power supply V Hz 230 1 50 Max rated current consumption A 2 86 3 61 4 01 Max power consumption kW 0 63 0 76 0 91 At 20 C 70 RH kW 0 48 0 60 0 68 C...

Page 8: ...8800 EDP no Unit with condensate pump 618505 618605 618805 1 DER Dehumidification output figure in accordance with DIN EN 810 2 Contains greenhouse gas according to Kyoto protocol 3 Noise level measur...

Page 9: ...different levels of humidity A B Fig 1 Corrosion rate in relation to relative humidity A Corrosion rate B Relative humidity It is evident that the corrosion rate below 50 rela tive humidity RH is low...

Page 10: ...our content in g m3 at humidity of C 40 60 5 1 3 1 9 10 3 8 5 6 15 5 1 7 7 20 6 9 10 4 25 9 2 13 8 30 12 9 18 2 C 80 100 5 2 6 3 3 10 7 5 9 4 15 10 2 12 8 20 13 8 17 3 25 18 4 23 0 30 24 3 30 3 Drying...

Page 11: ...erature continues to fall the capacity for the maximum possible volume of water vapour is reduced so much so that it is ultimately equal to the volume of water vapour contained in the air This tempera...

Page 12: ...al damage such as that caused by mould must be prevented The units may be used for the drying and dehumid ification of areas such as n New buildings industrial buildings n Basements storage rooms n Ar...

Page 13: ...2 1 4 3 5 A B Fig 5 Air dehumidification operating principle A Dehumidified room air B Moist room air 1 Fan 2 Condenser 3 Evaporator 4 Compressor 5 Condensate container 13...

Page 14: ...put of the unit is entirely dependent on the conditions inside the room room tempera ture relative humidity and observance of the set up instructions n The units may not be used in environments contai...

Page 15: ...cable may only be carried out by authorised electricians sub ject to the length of the cable connected load of the unit and taking into consideration how the unit is used at its location CAUTION All c...

Page 16: ...follows 1 Plug the unit s power plug into a properly installed and fused mains socket 230V 50 Hz If you connect the dehumidifier to the mains the unit should be switched off not oper ating The segment...

Page 17: ...erts to the pre vious setting n The adjustment steps for the target humidity are 5 RH per key press The adjustment range for the target humidity should lie between 30 and 70 RH If the humidity lies be...

Page 18: ...or the electrical power con sumed by the unit The display shows values from 0 0 to 99999 9 7 COMP ON INDICATOR If the compressor is running this indicator is illumi nated If the compressor is stops t...

Page 19: ...inute 10 RT C INDICATOR If the ROOM TEMP key is pressed the RT indi cator 10 illuminates for 5 seconds 11 FULL TANK DISPLAY If the water tank is full the FULL TANK and CHECK indicators illuminate The...

Page 20: ...OFF OFF OFF Flashes C Defrost LED OFF OFF OFF Flashes ON If Te 3 C then OFF OFF D Full Tank LED OFF OFF OFF OFF OFF Flashes E Solenoid valve OFF OFF ON for 10 sec then OFF OFF ON If Te 3 C then OFF OF...

Page 21: ...e ambient tem perature 3 Place the container carefully outside the unit and pull of the sealing cover A of the pouring opening B A B 4 Pour the water into a drain 5 Close the pouring opening B and car...

Page 22: ...side This provides the power supply for the condensate pump E Fig 13 Condensate tank at the rear The following steps should be carried out for unit operation with condensate pump 1 Remove the condensa...

Page 23: ...the condensate pump runs for an extended period of time the condensate tank must be checked for contamination at regular intervals Unit operation with a condensate tank without pump is possible at an...

Page 24: ...wer than the relative humidity in the room The red CHECK malfunction indicator light illuminates The cooling cycle is overloaded or overheated see CHECK indicator on page 18 Before starting the unit a...

Page 25: ...erature Rt 9 Shutdown Actuate the ON OFF key the COMP ON indi cator must extinguish If the units are inactive for longer periods discon nect them from the mains power supply Empty the condensate conta...

Page 26: ...bris n Only clean the units with a dry or moistened cloth n Never subject to direct jets of water e g pressure washers etc n Never use abrasive or solvent based cleaners n Even with heavy contaminatio...

Page 27: ...or similar NOTICE When cleaning the exchanger particular care must be taken because the fine aluminium fins bend very easily 5 Never subject to direct jets of water 6 Rinse with clean water to remove...

Page 28: ...ed All fastening screws checked Electrical safety check Test run Comments 01 Date Signature 02 Date Signature 03 Date Signature 04 Date Signature 05 Date Signature 06 Date Signature 07 Date Signature...

Page 29: ...0 60 80 5 6 4 3 2 1 7 8 9 10 11 12 13 14 15 16 17 19 18 20 21 22 23 24 25 26 27 28 29 30 31 25 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 50 51 52 53 54 49 We reserve the right to modify the d...

Page 30: ...ive clutch 15 Fan motor 16 Hose clamp 3 8 x 12 mm with O ring 17 Condensate container cpl 18 Taper plug 19 Magnetic float compl 20 Dry filter 21 Humidity temp probe cover 22 Humidity temp probe 23 Hum...

Page 31: ...Rear wall housing parts 48 Stand 49 Rubber stopper stand 2 pieces set 50 Strain relief 51 Axle 52 Axle fastening plate 53 Rubber stopper base plate 4 pieces set 54 Mains cable with plug Spare parts n...

Page 32: ...w drawing 29 Exploded view of the unit 29 L Locations for use 12 M Maintenance 26 Malfunction 24 O Operating sequence 12 Operational malfunctions 24 Ordering spare parts 30 R Relative air humidity 10...

Page 33: ...33...

Page 34: ...REMKO LTE 34...

Page 35: ......

Page 36: ...t as advisers to our customers in air conditioning and heating technology SFlbCustomer Service Our equipment operates precisely and reliably However in the event of a fault REMKO customer service is q...

Reviews: