2
Technical data
2.1 Unit data
Unit type
Cooling mode
System
Brine/water,
or water/water
Medium flow rate water (according to EN 14511, at ∆t 5 K)
m
3
/h
0.95
Min./max. operating temperature
°C
7/95
Max. operating pressure
bar
3
Power supply
V/Ph/Hz
230/1~/50
Brine-side pressure loss
kPa/bar
140/0.14
Heating side pressure loss
kPa/bar
140/0.14
WSP 80/110 connections
Inches
1", flat-sealing
WSP 140/180 connections
Inches
1 1/4", flat-sealing
Cooling mode dimensions
Height
mm
450
Width
mm
650
Depth
mm
150
Technical data for 3-way changeover valve
Cvs value (pressure loss 1 bar)
m
3
/h
7.5
Rated pressure
bar
10
Switching time
s
8
Medium connectors
Inches
1 1/4"
Electrical connection
V/Ph/Hz
230/1~N / 50
Power consumption
W
5 (4.8 VA max.)
Voltage resistance of the auxiliary contacts
A/V
1/250
Permissible environmental temperatures
°C
0-55
Min./max. hot water temperatures
°C
0-95
Rated pressure gauge
DN
25
EDP no.
260072
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.