background image

Commissioning

Control panel and information on commis-

sioning

 NOTICE!

Before commissioning, the complete system

hydraulics must be flushed and filled in accord-

ance with standards. If a drinking water storage

tank is installed, this must likewise be filled

before commissioning.

The Smart-Control Touch is used to operate and

control the complete heating system. The Smart

Control Touch is operated via the touch display.

n

The unit is pre-installed at the factory. After a

reset of the Smart Control, the default parame-

ters are loaded.

n

An intensive visual inspection is to be carried

out before the actual commissioning.

n

Switch on the power supply.

n

The pre-installed data is then loaded and the

parameters can be set using the commis-

sioning wizard or in the system configuration.

You can find information on this in the separate

operating instructions of the Smart Control.

Additional information on the functional and

operation, refer to the Smart-Control manual.

Care and maintenance

Regular care and maintenance assure fault-free

operation and long service life for the heat pump

system.

Care

n

The heat pump must be kept free of dirt and

other deposits.

n

The unit is to be cleaned with a damp cloth. In

doing so, ensure that no caustic, abrasive or

solvent-based cleaning products are used. Use

of powerful water jets is to be avoided.

Cleaning the heat source site

 NOTICE!

A dirt trap must be installed in the heat source

inlet of the heat pump to protect the evaporator

against contamination.

The filter screen of the dirt trap should be cleaned

one day after commissioning. Further checks

should be determined according to the level of pol-

lution. If no more impurities are visible, the filter of

the dirt trap can be removed to reduce the pres-

sure losses.

Maintenance

n

To perform the statutory leak test where appli-

cable, it is necessary to arrange a yearly main-

tenance contract with an appropriate specialist

firm.

Leak test

According to Regulation (EC) No. 842/2006, all

refrigeration systems containing a refrigerant filling

quantity of at least 2.4 kg, with “hermetically

sealed” refrigeration systems of at least 4.7 kg,

must be checked for leaks by the operator yearly.

The leak test must be documented and kept for at

least 5 years. The checks must be carried out by

certified personnel in accordance with Regulation

(EC) No. 1516/2007.

 NOTICE!

If the refrigerant capacity of 2.4 or 4.7 kg is

exceeded, an annual leak testing must be made

of the refrigerant circuit by a firm specialising in

this field. A heat pump should always be serv-

iced yearly. Therefore, we recommend

arranging for a service contract that includes

the leak inspection.

 

 

 

 

 

19

Summary of Contents for KNGcooling module

Page 1: ...Installation instructions Read the instructions prior to performing any task REMKO cooling module Cooling module for the WSP heat pump range 0261 2020 03 Edition 1 en_GB...

Page 2: ...ead these operating instructions carefully before commis sioning using this device These instructions are an integral part of the system and must always be kept near or on the device Subject to modifi...

Page 3: ...tion and changes 5 1 9 Intended use 5 1 10 Safety conscious working 6 1 11 Warranty 6 1 12 Transportation and packaging 6 1 13 Environmental protection and recycling 6 2 Technical data 7 2 1 Unit data...

Page 4: ...fatal or cause serious injury WARNING This combination of symbol and signal word warns of a potentially hazardous situation which if not avoided may be fatal or cause serious injury CAUTION This comb...

Page 5: ...s n The setup connection and operation of the units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable...

Page 6: ...d make a note of any damage or missing parts on the delivery note Inform the forwarding agent and contractual partner Claims under guarantee made at a later date will not be accepted WARNING Plastic f...

Page 7: ...hes 1 1 4 flat sealing Cooling mode dimensions Height mm 450 Width mm 650 Depth mm 150 Technical data for 3 way changeover valve Cvs value pressure loss 1 bar m3 h 7 5 Rated pressure bar 10 Switching...

Page 8: ...15 16 4 1 4 15 2 6 23 18 7 7 0 Cooling capacities of the WSP 140 WSP 180 heat pumps Inlet temperat WSP C Outlet temperat WSP C Air volume flow WSP m3 h Brine circuit temperature C Cooling capacity kW...

Page 9: ...0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 3 2 3 4 3 6 Q m h 0 10 20 30 40 50 W P1 2 1 3 3 4 Fig 1 Circulation pump Grundfoss UPM 3 25 70 130 capacity range 1 Pressure kPa 2 Height m 3 Medium flow rat...

Page 10: ...85 130 220 130 85 G 1 WSP 80 110 G 1 WSP 140 180 150 65 60 123 100 650 450 27 Fig 2 Unit dimensions all measurements in mm We reserve the right to modify the dimensions and design as part of the ongoi...

Page 11: ...oling capacity that is available is limited entirely to the source capacity and should be checked accordingly to ensure that it is suitable for the purpose Depending on the type and version of the sou...

Page 12: ...oor unit s I O module To do this unplug the plug installed for this from the I O mod ule s terminal block and replace it with the S 13 plug that is already attached to the probe cable from the cooling...

Page 13: ...ver valve the hydraulic connection for the valve 1 that is to be replaced must be closed and bled accordingly After bleeding you can loosen the three valve 1 screw connections After replacing one or b...

Page 14: ...e pipe network before connecting the heat pump n The heating cooling system provided by the customer must be protected to prevent the temperature falling below the dew point con densation water The RE...

Page 15: ...site must be planned and installed by the installation contractor M M M M B AB A12 A B AB A S 13 A12 S 08 A10 B AB A S 09 A 04 S 08 A 22 23 A 10 A B C1 2 3 1 D C2 E B AB A12 A B AB A S 13 A12 A Heat p...

Page 16: ...0 S D N G 2 0 S Sensor Inputs D N G 3 0 S D N G 4 0 S D N G 5 0 S D N G 6 0 S D N G 7 0 S D N G 8 0 S Sensor Inputs D N G 9 0 S D N G 0 1 S 1 S D N G 1 D N G 2 1 S D N G 3 1 S D N G 4 1 S D N G 5 1 S...

Page 17: ...be made at expert level To do so touch the REMKO logo in the upper right corner of the display User level Activate Expert level by touching the REMKO logo at the top right Password input using Passwor...

Page 18: ...the pressure gauge n Make sure that all valves of the heating system and the distributors are open to guarantee the free medium flow rate n Check the direction of flow of the heating cycle indicated o...

Page 19: ...ure that no caustic abrasive or solvent based cleaning products are used Use of powerful water jets is to be avoided Cleaning the heat source site NOTICE A dirt trap must be installed in the heat sour...

Page 20: ...ter the brine cycle Check the brine level or filling pressure of the brine cycle and the pre pressure of the dia phragm expansion vessel at regular intervals You can read the filling pressure of the b...

Page 21: ...d spare parts Exploded view of the unit 1 3 2 3 2 4 Spare parts list No Designation EDP no 1 Heat exchanger 2 Actuator for 3 way valve 1120912 3 Hydraulic bottom part 1 1120912 1 4 SMT PT1000 brine re...

Page 22: ...M Maintenance 19 O Operating the controller 17 P Packaging disposal 6 R Recycling 6 Removing the actuator 13 S Safety Dangers of failure to observe the safety notes 4 General 4 Identification of note...

Page 23: ......

Page 24: ...5232 606 260 E mail info remko de URL www remko de REMKO GmbH Co KG Klima und W rmetechnik Im Seelenkamp 12 32791 Lage Hotline within Germany 49 0 5232 606 0 Hotline International 49 0 5232 606 130 W...

Reviews:

Related manuals for KNGcooling module