9.2.6
Setting the manual mode
In some cases, it may be necessary to set the boiler to manual mode, for
example when the controller has not yet been connected. The boiler can
be set to automatic or manual mode via the symbol. Proceed as follows:
1. Press the two keys at the same time and then press the key
until the symbol flashes in the menu bar.
2. Press the
key; the display will show:
either the text
with the current water pressure (only if a water
pressure sensor is connected).
or the minimum flow temperature value.
3. Press the or keys to temporarily increase this value in manual
mode.
4. To confirm, press the
key.
The boiler is now set to manual mode.
5. Press the
key twice to leave this menu and return to the opera
tion display.
9.3
Displaying the measured values
The control unit continually registers various values from the boiler and the
connected sensors. These values can be read on the control panel of the
boiler.
9.3.1
Reading the various current values
The following current values can be read in the information menu :
= Status.
= Sub-status.
= Flow temperature (°C).
= Return temperature (°C).
= Calorifier temperature (°C).
= Outside temperature (°C) (only with outside sensor).
= Solar boiler temperature (°C).
= Internal set point (°C).
= Ionisation current (μA).
= Fan speed (rpm).
= Water pressure (bar (MPa)).
= Supplied relative heat output (%).
The current values can be read as follows:
Fig.56
Setting manual mode
AD-0000080-01
2x
2x
bar
9 Settings
58