Supplied By www.heating spares.co Tel. 0161 620 6677
18
Remeha Gas 360 S
20/07/05 - 300005180-001-A
Commissionning
1 Pressure settings and calibrated nozzle markings
1.1
Table of pressure settings and nozzle markings
1.2
Flow table (15°C - 1013 mbar)
Boiler type Gas 360 S/
8
10
12
14
Nozzle pressure
Natural gas H
mbar
14
14
14
14
Propane
mbar
36
36
36
36
Start-up pressure
Natural gas H
mbar
11
11
11
11
Propane
mbar
10
10
10
10
Nozzle
Number of nozzles
7
9
11
13
Nozzle markings natural gas H/E
257B
257B
257B
257B
Marking, propane nozzles
160B
160B
160B
160B
Boiler type Gas 360 L /
8
10
12
14
Natural gas H
2nd stage
m
3
/h
7.29
9.35
11.41
13.46
Propane
2nd stage
kg/h
5.35
6.87
8.37
9.88