Code
Display text
Description
Range
Gas 120
ACE - 65
Gas 120
ACE - 90
Gas 120
ACE - 115
GP022
Tfa Filter Tau
Tau factor for average flow
temperature calculation
1 - 255
1
1
1
PP014
ChPumpDTRedu
ction
Reduction of temperature delta
modulating for pump
modulation
0 °C - 40 °C
18
18
18
PP016
Max. CH pump
speed
Maximum central heating pump
speed (%)
20 % - 100 %
100
100
100
PP017
ChPumpSpeedM
axFactor
Maximum central heating at
minimum load as percentage of
max pump speed
0 % - 100 %
100
100
100
PP018
Min CH pump
speed
Minimum central heating pump
speed (%)
20 % - 100 %
30
30
30
PP023
Start hysteresis
CH
Hysteresis to start burner in
heating mode
1 °C - 10 °C
10
10
10
9.10.4 List of parametersSCB-02
Tab.36
Parameter
Text display
Description
Factory
setting
CP000
MaxZoneTFlowSetpoin
t
Maximum Flow Temperature setpoint zone
Adjustment range:
from 7 °C to 90 °C
90
CP001
MaxZoneTFlowSetpoin
t
Maximum Flow Temperature setpoint zone
Adjustment range:
from 7 °C to 90 °C
55
CP010
Tflow setpoint zone
Zone flow temperature setpoint, used when the zone is set to a fixed flow
setpoint.
Adjustment range:
from 7 °C to 95 °C
90
CP011
Tflow setpoint zone
Zone flow temperature setpoint, used when the zone is set to a fixed flow
setpoint.
Adjustment range:
from 7 °C to 95 °C
50
CP020
Zone Function
Functionality of the zone
Adjustment range:
0 =Disable
1 =Direct
2 =Mixing Circuit
3 =Swimming pool
4 =High Temperature
5 =Fan Convector
6 =DHW tank
7 =Electrical DHW
8 =Time Program
9 =ProcessHeat
10 =DHW Layered
11 =DHW Internal tank
12 =DHW Commercial Tank
31 =DHW FWS EXT
6
9 Settings
52