When you have saved the commissioning settings, the option Revert
commissioning settings is available in the Advanced Service Menu.
9.7
Resetting or re-establishing the parameters.
9.7.1
Resetting after replacing the PCB
Configuration numbers must be reset if the boiler or burner safety unit
PCB is replaced.
The configuration numbers can be found on the data plate of the boiler.
To reset the configuration numbers:
1. Press the key.
2. Select Advanced Service Menu > Set Configuration Numbers.
3. Select CU-GH-08.
4. Select and change the CN1 setting.
5. Select and change the CN2 setting.
6. Select Confirm to confirm the modifications.
9.7.2
Auto-detecting options and accessories
Use this function after replacing a boiler PCB in order to detect all the
devices connected to the CAN bus.
To detect devices connected to the CAN bus:
1. Press the key.
2. Select Advanced Service Menu > Auto Detect.
3. Select Confirm to carry out the auto-detect.
9.7.3
Reverting to the commissioning settings
If the commissioning settings were saved, you can revert to the values
specific to your installation.
To revert to the commissioning settings
1. Press the key.
2. Select Advanced Service Menu > Revert commissioning settings.
3. Select Confirm to revert to the commissioning settings.
9.7.4
Reverting to the factory settings
To revert to the factory settings for the boiler:
1. Press the key.
2. Select Advanced Service Menu > Reset to Factory Settings.
3. Select Confirm to revert to the factory settings.
9.8
Accessing information on the hardware and software versions
Information on the hardware and software versions for the appliance's
various components is stored in the control panel.
To access:
1. Press the key.
2. Select Version Information.
3. Select the component for which you would like to see the version
information.
Component
Description
Appliance Info
Information about the boiler
CU-GH-08
Information about the boiler central unit PCB
MK3 -
HMI T-control
Information about the control panel