3. Set the following parameters:
Parameters
Description
Zone screed drying
Number of days of drying (1)
ScreedStartTemp
Drying start temperature (2)
ScreedStopTemp
Drying end temperature (3)
The screed drying programme will start immediately and continue for the
selected number of days.
At the end of the programme, the selected operating mode will restart.
Tab.29 Example: Adjustment of the temperature setting every 7 days
Days
Start temperature
End temperature
Temperature variation
1 to 7
+25 °C
+55 °C
Temperature increased every day by 5 °C
8 to 14
+55 °C
+55 °C
Temperature maintained at +55 °C without dropping at night
15 to 21
+55 °C
+25 °C
Temperature decreased every day by 5 °C
9.4
Configuring the maintenance message
The boiler control panel is used to display a message whenever a service
is necessary.
To configure the maintenance message:
1. Select the Maintenance
icon.
2. Select Service notification.
3. Select the desired type of notification:
Type of notification:
Description
None
No maintenance message
Custom notification
The maintenance message will be displayed once the burner operating hours defined
by the Service Burning hrs parameter have elapsed
ABC notification
Recommended setting
The maintenance message will be displayed according to the power input (energy val
ue):
Gas 120 ACE - 65 : 90,000 kWh
Gas 120 ACE - 90 : 135,000 kWh
Gas 120 ACE - 115 : 180,000 kWh
9.5
Saving the installer details
The name and phone number of the installer can be saved so that the
user can find it easily.
1. Press the key.
2. Select System Settings > Installer Details.
3. Enter the name and phone number.
9.6
Saving the commissioning settings
You can save all installation-specific settings. These settings can be
restored if necessary, for example after replacement of the main electronic
control system board.
1. Press the key.
2. Select Advanced Service Menu > Save as commissioning settings.
3. Select Confirm to save the settings.
Fig.57
MW
-5
0
0
0
7
6
4
-1
10
9
8
7
6
5
4
3
2
1
23
20
26
29
32
35
38
41
44
47
° C
00:00
00:00
00:00
1
2
3
On
On
On
9 Settings
46
MID _HMI T-control - Gas 120 ACE
7717201 - v03 - 25062019